5-2
Section
Setting Data Links
71
5-2-4 Automatic Setting: “Select All”
Data links can be automatically created by setting values in the DM parameter
area of the PC’s CPU Unit of the startup node. The settings are made using a
Programming Console “or the SYSMAC Support Software.
The startup node is the node from which the data links are activated. When auto-
matically setting data links, data link operation is based on the values set in the
startup node.
DM parameter area
Startup node
CPU Unit
Or
Programming Console
Controller Link
Support Software
IBM PC/AT or
compatible
Controller Link
Note
1. Parameters for automatically setting data links can only be set in PCs. Refer
to the Controller Link Units Operation Manual (W309) for details.
2. A computer (Controller Link Support Board) cannot be the startup node for
an automatically setting data links.
3. A computer can participate in automatically set data links. Data link tables
are not required in the computer (the data link tables in the startup node will
be used).
5-2-5 Automatic Setting Example
This section shows an example of DM parameter area settings and the data link
areas that are created as a result.
Set the parameters in the startup node as follows:
Data link mode: Automatic
First data link status word: IR 310
Participating nodes: #1, #2, and #3
Area 1 data link start word: LR 00
Number of words: 10
Area 2 data link start word: DM 1000
Number of words: 200
DM Parameter Area
Settings