![Omron SYSMAC 3G8F7-CLK12-E Operation Manual Download Page 90](http://html1.mh-extra.com/html/omron/sysmac-3g8f7-clk12-e/sysmac-3g8f7-clk12-e_operation-manual_1633420090.webp)
5-3
Section
Starting and Stopping Data Links
74
CV-series Startup Node
Data link Start Bit
Start: Changed from OFF to ON or set to ON
when power is turned on
Stop: Changed from ON to OFF
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Word N
N: DM 2000 + 100
×
(unit number)
5-3-2 Using the Controller Link Support Software
Data links can be started or stopped using from the command on the Data Link
Menu of the Controller Link Support Software. The node for which starting and
stopping is being specified must participate in the data links.
Using a Programming Device Connected to PC Node
Node in data links
Start/stop data links
Controller Link
Support Software
IBM PC/AT or
compatible
Using a Computer Node with FinsGateway
IBM PC/AT or
compatible
FinsGateway
Start/stop specified
directly to Controller
Link Support Board.
5-3-3 Using FINS Commands
Data links can be started and stopped by sending the DATA LINK START and
DATA LINK STOP FINS commands from a node on the Controller Link to a node
that is in the data links.
Sending FINS Commands from a Computer Node
FINS command:
DATA LINK START/
DATA LINK STOP
IBM PC/AT or
compatible
Node in data links
Issuing the FINS Command from CV-series and CS1-series PCs
Node in data links
FINS command:
DATA LINK START/
DATA LINK STOP
CV