![Omron SYSMAC 3G8F7-CLK12-E Operation Manual Download Page 151](http://html1.mh-extra.com/html/omron/sysmac-3g8f7-clk12-e/sysmac-3g8f7-clk12-e_operation-manual_1633420151.webp)
Section
9-3
Error Log
135
Error
code
Recorded
in
EEPROM
Correction
Detail code
Contents
Error
code
Recorded
in
EEPROM
Correction
2nd byte
1st byte
Contents
0101
Hex
Transmission failed; local node
not in Network
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Refer to 9-1 Troubleshooting
Using Indicators and place the
local node into Network.
No
0103
Hex
Transmission failed; retry count
exceeded
Bits 8 to 14:
Source Network
address
Bit 15:
OFF
Response block
Using the Controller Link Support
Software or FINS commands, run
echoback test and check
operating environment if errors
occur.
No
0104
Hex
Transmission failed; maximum
number of frames exceeded.
Response block
Bits 0 to 7:
Destination node
address
Bits 8 to 14:
Destination Network
Check event status on the
network. Reduce the number of
events per communications cycle
or increase the maximum number
of network parameter frames.
No
0105
Hex
Transmission failed; node
address incorrect
Destin tion Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
d b
bi
)
Refer to the Installation Guide and
check node address settings to
be sure they are within range and
unique.
No
0106
Hex
Transmission failed; redundant
node address
(
y
2nd byte, bits 0 to 7)
Correct node addresses so that
they are unique within the same
Network.
No
0107
Hex
Transmission failed; destination
node not in Network
Refer to 9-1 Troubleshooting
Using Indicators and place
destination node into Network.
No
0108
Hex
Unit missing; cannot execute.
Refer to the Installation Guide and
check the Controller Link unit
number.
No
0109
Hex
Transmission failed; destination
busy
Increase number of retries or
reconfigure system to distribute
load.
No
010A
Hex
Transmission failed;
communications controller error
Conduct an echoback test and if
the effects of noise are
considerable, reconsider the
operating environment. Restart
the computer. If the error occurs
again, replace the Board.
Yes
010B
Hex
CPU Unit error; cannot send.
Refer to the manuals for the CPU
Unit and correct the problem. If
the problem cannot be corrected,
replace the CPU Unit.
No
010C
Hex
Unit number setting error;
cannot send.
Refer to the Installation Guide and
check node address settings to
be sure they are within range and
unique.
No