The example of a time chart
[Example
1
] Here, the case where the following conditions.
Setting conditions
Operation
:client shutdown / UPS stop
Waiting time
(Min)
:10(
Initial value
)
1st warning (Sec)
:30(
Initial value
)
Warning period (Sec)
:30(
Initial value
)
Waiting time to a UPS stop
(Sec)
:180(
Initial value
)
The day of the week/time of shutdown execution :Mon 22:20:00
The reboot setting day of the week / time
:Tue 9:00:00
The setting conditions of a client computer
Time required for the end of application software :30 sec(
Initial value
)
22 : 10 : 00
22 : 20 : 00
22 : 23 : 00
09: 00 : 00
Mon.
Mon.
Tue.
UPS ON
UPS OFF
Warning
sending by
60sec interval
The end of waiting time.
shutdown
command sending to a client
computer
UPS stop
UPS start
22 : 20 : 30
Mon.
Tue.
client
computer
ON
client
computer
OFF
Shutdown command
reception
The end of
waiting time.
Shutdown
start
Power off
Reboot