The example of a time chart
[Example
1
] Here, the case where the following conditions
are set up is illustrated.
Setting conditions
Operation
:client shutdown / UPS stop
Waiting time (Min)
:10(
Initial value
)
1st warning (Sec)
:30(
Initial value
)
Warning period (Sec)
:30(
Initial value
)
Waiting time to a UPS stop
(Sec)
:180(
Initial value
)
AC failure occurring time
:22:20:00
The setting conditions of a client computer
Time required for the end of application software :30 sec(
Initial value
)
22 : 20 : 00
22 :30 :00
22 : 33 : 00
UPS ON
UPS OFF
Warning sending
by 30sec interval
AC failure occurring
The end of waiting
time
shutdown command
sending to a client
computer
UPS stop
22 :30 :30
client
computer
ON
client
computer
OFF
Shutdown command
reception
OS stop
The end of waiting
time
Shutdown start
Power off
72