The detail description of a screen
1.
The Number of Shutdown by Script
After entering the number of devices which you want to shut it
down by using a script and press the Set
Value
button.
2.
Load Device
The arbitrary character strings which identify and explain the
apparatus which wants to perform a script shutdown are inputted.
3.
IP Address
The IP address of apparatus which wants to perform a script
shutdown is inputted.
4.
User Name
A user name effective in login of apparatus which wants to perform
a script shutdown is specified.
5.
Password
A password effective in login of apparatus which wants to perform
a script shutdown is specified.
6.
Retry Times
It is arbitrarily specifies the number of times of the retry at the time
of login failure.
7.
Time Out (sec)
It is arbitrarily sets up the timeout time in the case of login.
8.
Wait time for run script (Sec)
It delays the start time of script shutdown.
9.
Select Script Number
The script performed when SC20G2 starts shutdown operation is
specified. A script is set up by the following clause "a script
setup."
1
1
.
Protocol
It specifies the communication method used by the SC20G2.
It supports t
wo
types of Telnet, SSH V2.
1
2
.
Result
The result of a script shutdown is displayed.
1
3
.
Test
By pushing a [Execution] button, for every setup, it can do the test
of a script shutdown of operation individually.
Please refer to the item of "Ping monitoring setting menu" for execution
of a script shutdown.
51
SSH protocol supports V2 only.
10.
Condition
It selects the condition to execute script.
AC Fail:It is executed when it shutdown by input power failure.
AC Recover: It is executed when it rebooted by AC recovery after
shutdown by ac failure.