![background image](http://html1.mh-extra.com/html/omron/sc20g2/sc20g2_operation-manual_742413055.webp)
The detail description of a screen
1.
Script Name
It set in any meaningful name to script, such as the target OS.
2.
Script form
A script to execute is described.
3.
Set Value
Descriptive content is saved by pressing the [Set Value] button.
Please refer to the item of "Ping monitor setting" for execution of a
script shutdown.
An initial (default) setup of each script is as follows.
"As for the contents, all are execution about the shutdown operation
after logging in to object apparatus."
Please refer to the following, when operation becomes unstable.
[
Script 1 : Windows
]
rcv=login:
snd=$u1
rcv=password:
snd=$p1
rcv=C:¥
snd=shutdown -s -f
[
Script 2 : Linux
]
rcv=login:
snd=$u1
rcv=Password
snd=$p1
rcv=]$
snd=$u2
rcv=Password:
snd=$p2
rcv=]#
snd=init 0
[
Script 3 : UNIX
]
rcv=login:
snd=$u1
rcv=Password:
snd=$p1
rcv=$
snd=$u2
rcv=Password:
snd=$p2
rcv=#
snd=shutdown -y -i0 -g10
[
Script 4 : Mac(OS X)
]
rcv=login:
snd=$u1
rcv=Password:
snd=$p1
rcv=$
snd=$u2
rcv=Password:
snd=$p2
rcv=#
snd=halt