6 Using the contact signal functions
6-2 SC07 Contact signal card specifications
BN50T/BN75T/BN100T/BN150T/BN220T/BN300T
6-4
6-2-4 Contact Signal circuit
Signal output (BL, TR, BU, WB)
UPS Stop Signal input (BS)
Remote ON/OFF
BL
TR
BU
WB
BS
COM
2.4V
560
Ω
10V
10K
Ω
Remote ON/OFF(+)
Remote ON/OFF(-)
6-2-5 Example of the use of the Contact Signal circuit
Example of BU signal output circuit and
the connected circuit
Example of BS signal input circuit
and the connected circuit
To port
on PC
4.7K
TLP521
Inside of
UPS
External
Circuit
+12V
1K
Ω
C2
C1
+5V
C1,C2 : 0 pF to several
thousand pF
(Consider the capacity according to the
operating environment.)
*
COM
UPS side
GND
C2458
BS
From port on PC
12V
1K
1.2K
TLP521
System side
Connecting cable
(twisted or shielded)
Remote ON/OFF circuit
Example of
remote ON/OFF
UPS side
remote ON/OFF(+)
remote ON/OFF(-)
6 Using the contact signal functions
6-2 SC07 Contact signal card specifications
BN50T/BN75T/BN100T/BN150T/BN220T/BN300T
6
6-5
6-2-6 Items that can be set using the contact signal card
Setting up when using the unit in the SC05 compatible mode
Jumper settings
By making jumper settings, the contact signal card SC05/06 connector pin assignments
can be changed.
Turn over the contact signal card, and change the contact signal card’s JP2 to JP9
jumper settings (8 settings) to "SC05/06".
JP10
JP2 to JP9
Jumper settings
(8 digits)
<Before change>
<After change>
SC05/06
SC07
SC05/06
SC07
Note 1: Use the [SC05/06/07] side for JP10
Note 2: Factory settings: SC07 side for JP2 to JP9, SC05/06/07 side for JP10
6-2-7 Insert method of contact signal card
1
. Remove the screws above and below the option slot (2 screws) on the back of the unit,
and remove the cover.
<BN50T/75T>
<BN100T/150T>
<BN220T/300T>
Summary of Contents for BN100T
Page 2: ......
Page 24: ...1 Preparation BN50T BN75T BN100T BN150T BN220T BN300T 1 8...
Page 36: ...2 Installation and connection BN50T BN75T BN100T BN150T BN220T BN300T 2 12...
Page 54: ...3 Check and start operation BN50T BN75T BN100T BN150T BN220T BN300T 3 18...
Page 72: ...4 Maintenance and Inspection BN50T BN75T BN100T BN150T BN220T BN300T 4 18...
Page 88: ...6 Using the contact signal functions BN50T BN75T BN100T BN150T BN220T BN300T 6 8...
Page 94: ...8 Troubleshooting BN50T BN75T BN100T BN150T BN220T BN300T 8 4...
Page 96: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 2 2 FA OA 2 AC 50 60Hz AC AC...
Page 97: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 9 3 AC AC 3P 2P AC AC 5cm UPS UPS...
Page 99: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 9 5 1mA AC UPS AC UPS...
Page 109: ...Cut here...