5 To perform shutdown processing of the devices when a power failure occurs
5-2 When using the included UPS monitoring software
BN50T/BN75T/BN100T/BN150T/BN220T/BN300T
5-6
2
. Install the included “PowerAct Pro” or “Simple Shutdown Software” to the PC you want
to shut down.
Note: Installation method:
For “PowerAct Pro”, refer to the installation guide (for Windows) on the CD-ROM.
Refer to the manual on the CD-ROM for “Simple Shutdown Software”.
Notes
The limitation on the commercial power stopped period when scheduled oper-
ation using the UPS monitoring software
When performing scheduled operation in which the UPS is stopped and a device
such as a breaker is used to stop the UPS at the same time that commercial power
stops, specify a period of no more than 3 months for the start of the next operation.
If you specify a period longer than 3 months, the internal timer is reset and the
scheduled operation does not start.
Note that this period reduces to approximately half when the battery is dead.
If a period of 3 months is exceeded, you start operation by supplying commercial
power and pressing the Start Switch. However, if the battery is dead, you may not
be able to start operation.
In this case, replace the battery according to "4-2 Replacing the battery".
When manually starting during the scheduled operation using the UPS moni-
toring software
To manually start up this unit after it has been stopped by a scheduled operation,
turn OFF the power switch and turn it back ON again.
To stop the unit when it is in operation, turn OFF the power switch.
Auto restart after OS closing processing using the UPS monitoring software
When the power is restored while auto shutdown processing is being per-
formed
If a power failure occurs and then the power is restored while auto shutdown is still
in progress, UPS output will stop temporarily after the set time elapses. After
shutdown is finished, do not turn on the computer until the UPS has finished
restarting.
Additional Information
When the power is restored after the UPS automatically stops during a power failure,
the UPS automatically restarts and supplies power.
If you do not want connected devices to operate, turn off the switch of the
connected devices or disable the auto reboot after power restoration setting (LCD
menu - [Setting] - [Boot Setting] - [Auto Reboot]).
Summary of Contents for BN100T
Page 2: ......
Page 24: ...1 Preparation BN50T BN75T BN100T BN150T BN220T BN300T 1 8...
Page 36: ...2 Installation and connection BN50T BN75T BN100T BN150T BN220T BN300T 2 12...
Page 54: ...3 Check and start operation BN50T BN75T BN100T BN150T BN220T BN300T 3 18...
Page 72: ...4 Maintenance and Inspection BN50T BN75T BN100T BN150T BN220T BN300T 4 18...
Page 88: ...6 Using the contact signal functions BN50T BN75T BN100T BN150T BN220T BN300T 6 8...
Page 94: ...8 Troubleshooting BN50T BN75T BN100T BN150T BN220T BN300T 8 4...
Page 96: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 2 2 FA OA 2 AC 50 60Hz AC AC...
Page 97: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 9 3 AC AC 3P 2P AC AC 5cm UPS UPS...
Page 99: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 9 5 1mA AC UPS AC UPS...
Page 109: ...Cut here...