10 References
10-3 Battery life
BN50T/BN75T/BN100T/BN150T/BN220T/BN300T
10-4
10-3 Battery life
Battery has a limited life span.
Periodic checks of the lead battery used in the battery unit are required due to the battery
limited lifespan. For the battery checking method, refer to "4-1 Checking the battery".
Battery replacement is recommended before the battery is expired.
Battery life
(The following is expressed based on the battery's trickle life, the service life of
a battery under the condition where low-frequent (once or twice a month) re-
chargings and dischargings are performed.)
Battery type
Expected battery life
(Ambient
temperature 40°C)
Expected battery life
(Ambient
temperature 30°C)
Expected battery life
(Ambient
temperature 25°C)
UPS Series
Long-life
battery
2 years
4 years
5 years
BN-T
Basically, the ambient temperature have a high influence on the battery life.
The periodic recharges are required even if the battery is stored.
The battery self-discharges even if the UPS is not used (i.e., leaving the battery not
charged), and it deteriorates the battery. In the worst case, the battery may become un-
usable.
• Example of the storing condition and recharging frequencies
Recharge line
Storage period (Month)
R
em
ai
ni
ng
cap
acit
y
(%)
<Description>
When the battery is stored at the storage temperature of 25°C, the battery self-discharges
(and the battery level lowers) to approximately 80% over half a year, and to approximately
50% over a year.
Higher the storage temperature is, faster the battery will self-discharge.
Storage temperature Auxiliary charging interval
40°C or less
2 months
30°C or less
4 months
25°C or less
6 months
10 References
10-4 Input voltage sensitivity settings
BN50T/BN75T/BN100T/BN150T/BN220T/BN300T
10-5
10
10-4 Input voltage sensitivity settings
The input voltage sensitivity settings and input/output voltages of the Uninterruptible Power
Supply (UPS) are related as shown in the table below.
Select an input voltage sensitivity setting that matches the specified input voltage range of
the connected device.
Input voltage sensitivity UPS input voltage range UPS output voltage range Input voltage sensitivity selection method
High
89 to 113 VAC
90 to 110 VAC
When you want to narrow the output
voltage range
Standard
89 to 118 VAC
90 to 114 VAC
When using in a regular environment
Low
84 to 118 VAC
84 to 114 VAC
When you want to reduce the frequency
of operation in Battery Mode.
Summary of Contents for BN100T
Page 2: ......
Page 24: ...1 Preparation BN50T BN75T BN100T BN150T BN220T BN300T 1 8...
Page 36: ...2 Installation and connection BN50T BN75T BN100T BN150T BN220T BN300T 2 12...
Page 54: ...3 Check and start operation BN50T BN75T BN100T BN150T BN220T BN300T 3 18...
Page 72: ...4 Maintenance and Inspection BN50T BN75T BN100T BN150T BN220T BN300T 4 18...
Page 88: ...6 Using the contact signal functions BN50T BN75T BN100T BN150T BN220T BN300T 6 8...
Page 94: ...8 Troubleshooting BN50T BN75T BN100T BN150T BN220T BN300T 8 4...
Page 96: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 2 2 FA OA 2 AC 50 60Hz AC AC...
Page 97: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 9 3 AC AC 3P 2P AC AC 5cm UPS UPS...
Page 99: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 9 5 1mA AC UPS AC UPS...
Page 109: ...Cut here...