3 Check and start operation
3-4 Operation from the LCD menu
BN50T/BN75T/BN100T/BN150T/BN220T/BN300T
3-14
Basic operations on the menu screen
Switch
Description
[
] [
]
Move cursor up/down or increase/decrease values
Select the menu item or set the value
Return to menu or cancel
3 Check and start operation
3-4 Operation from the LCD menu
BN50T/BN75T/BN100T/BN150T/BN220T/BN300T
3-15
3
3-4-2 The menu list of LCD
Display language can be selected from Japanese (default) or English.
The menu displayed changes with menu type setup. There are a Standard type and an
Advanced type. A Standard type (default) is for general purpose.
An Advanced type is for administrators.
Additional Information
• If you want to display the LCD in English, set the “Settings” - “Local Setting” -
“Language” setting in the menu on the unit’s LCD.
• If you want to display the LCD in Advanced menu type, set the “Setting” - “Local
Setting” - “Menu Type” setting in the menu on the unit’s LCD.
*: Displayed only when the UPS is stopped. (Not displayed during operation.)
Menu
Description
Contents
Menu
type
Meas-
urements
Load Meter
Display the applied load in VA
and W.
Load Meter:
0 to xxxx W
0 to xxxx VA
Standard
Input/Output Meter
Display the input/output voltage
and frequency.
Input/Output Meter:
Input: 0 to xxx.x V, 0 to xx.x Hz
Output: 0 to xxx.x V, 0 to xx.x Hz
Battery Meter
Display the status of the built-in
battery.
Battery Meter:
Charge Rate: 0 to 100%
Voltage: 0.0 to xxx.xV
Runtime: 0.0 to xxx min
Longevity
Display the estimated lifespan
of the UPS in 5 levels.
Longevity:
UPS: display with a five-level indicator
Battery: display with a five-level
indicator
Cumulat. Power Usage Display the amount of power
used so far and the number of
days elapsed.
Cumulat. Power Usage:
Total: 0 to xxxx kWh
Period: 0 to xxxx days
Advanced
Average Power Usage
Display the average amount of
power used so far.
Average Power Usage:
0 to xxxx Wh
Control
Start Function Test
Perform a self-diagnosis and a
test to check for battery deteri-
oration, and then display the
results.
Start Function Test
·
Passed Battery OK
·
Failed No Battery
·
Failed Battery Weak
·
Canceled UPS is on Battery mode
·
Canceled B.capacity is not enough
Standard
Reset B.life counter
Reset the battery life counter.
Reset B.life ctr:
Are you sure?
Yes or No
Load Segments
Control the ON/OFF of output
receptacle group B and C.
Load Segments
Out B: ON/OFF
Out C: ON/OFF
Advanced
Reset Power Usage
Reset the values of cumulative
power usage and average
power usage.
Reset power usage
Are you sure?
Yes or No
Dry Contact Test *
Perform a contact test when
using a contact signal card
(SC07/SC08).
Dry Contact Test
BU: ON/OFF
BL: ON/OFF
TR: ON/OFF
WB: ON/OFF
Initialization *
Return each of the UPS set-
tings to the factory settings.
Restore F.setting
Are you sure?
Yes or No
Maintenance Bypass
Move to Bypass Mode forcibly. Maintenance Byp.
Are you sure?
Yes or No
Setting
Local
Setting
Language
Set the language to be dis-
played on the LCD.
Language:
Japanese (Default),
English
Standard
LCD Setting Change the contrast of the
LCD.
LCD Setting:
Contrast bar
Summary of Contents for BN100T
Page 2: ......
Page 24: ...1 Preparation BN50T BN75T BN100T BN150T BN220T BN300T 1 8...
Page 36: ...2 Installation and connection BN50T BN75T BN100T BN150T BN220T BN300T 2 12...
Page 54: ...3 Check and start operation BN50T BN75T BN100T BN150T BN220T BN300T 3 18...
Page 72: ...4 Maintenance and Inspection BN50T BN75T BN100T BN150T BN220T BN300T 4 18...
Page 88: ...6 Using the contact signal functions BN50T BN75T BN100T BN150T BN220T BN300T 6 8...
Page 94: ...8 Troubleshooting BN50T BN75T BN100T BN150T BN220T BN300T 8 4...
Page 96: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 2 2 FA OA 2 AC 50 60Hz AC AC...
Page 97: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 9 3 AC AC 3P 2P AC AC 5cm UPS UPS...
Page 99: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 9 5 1mA AC UPS AC UPS...