10 References
10-3 Battery life
BN50T/BN75T/BN100T/BN150T/BN220T/BN300T
10-4
10-3 Battery life
Battery has a limited life span.
Periodic checks of the lead battery used in the battery unit are required due to the battery
limited lifespan. For the battery checking method, refer to "4-1 Checking the battery".
Battery replacement is recommended before the battery is expired.
Battery life
(The following is expressed based on the battery's trickle life, the service life of
a battery under the condition where low-frequent (once or twice a month) re-
chargings and dischargings are performed.)
Battery type
Expected battery life
(Ambient
temperature 40°C)
Expected battery life
(Ambient
temperature 30°C)
Expected battery life
(Ambient
temperature 25°C)
UPS Series
Long-life
battery
2 years
4 years
5 years
BN-T
Basically, the ambient temperature have a high influence on the battery life.
The periodic recharges are required even if the battery is stored.
The battery self-discharges even if the UPS is not used (i.e., leaving the battery not
charged), and it deteriorates the battery. In the worst case, the battery may become un-
usable.
• Example of the storing condition and recharging frequencies
Recharge line
Storage period (Month)
R
em
ai
ni
ng
cap
acit
y
(%)
<Description>
When the battery is stored at the storage temperature of 25°C, the battery self-discharges
(and the battery level lowers) to approximately 80% over half a year, and to approximately
50% over a year.
Higher the storage temperature is, faster the battery will self-discharge.
Storage temperature Auxiliary charging interval
40°C or less
2 months
30°C or less
4 months
25°C or less
6 months
Summary of Contents for BN100T
Page 2: ......
Page 24: ...1 Preparation BN50T BN75T BN100T BN150T BN220T BN300T 1 8...
Page 36: ...2 Installation and connection BN50T BN75T BN100T BN150T BN220T BN300T 2 12...
Page 54: ...3 Check and start operation BN50T BN75T BN100T BN150T BN220T BN300T 3 18...
Page 72: ...4 Maintenance and Inspection BN50T BN75T BN100T BN150T BN220T BN300T 4 18...
Page 88: ...6 Using the contact signal functions BN50T BN75T BN100T BN150T BN220T BN300T 6 8...
Page 94: ...8 Troubleshooting BN50T BN75T BN100T BN150T BN220T BN300T 8 4...
Page 96: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 2 2 FA OA 2 AC 50 60Hz AC AC...
Page 97: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 9 3 AC AC 3P 2P AC AC 5cm UPS UPS...
Page 99: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 9 5 1mA AC UPS AC UPS...
Page 109: ...Cut here...