3 Check and start operation
3-4 Operation from the LCD menu
BN50T/BN75T/BN100T/BN150T/BN220T/BN300T
3-16
*: Displayed only when the UPS is stopped. (Not displayed during operation.)
Menu
Description
Contents
Menu
type
Setting
Local
Setting
LCD Auto
OFF
Set the amount of time after
which the LCD turns off auto-
matically.
LCD Auto OFF:
· Always ON
· Auto OFF after 30sec. (Default)
· Auto OFF after 3min.
Standard
LCD Test
Check that the LCD and
LEDs light up.
LCD Test:
Execute
Audible
Alarm
Set the beeper status.
Audible Alarm:
· ON (Default)
· OFF at Battery Mode
· OFF at Anytime
Calendar
Setting
Set the calendar information for
the UPS.
Calendar Setting:
Year, Month, Day, Hour, Min
UPS
Installation
Set the date you started using
the UPS.
UPS Installation:
Year, Month, Day
(Default: 2000/1/1)
UPS Life
Count
Set the UPS life counter status. UPS Life Count:
· Enable (Default)
· Disable
Menu Type Select the menu to be dis-
played. "Standard" displays
frequently used items only.
Menu Type:
· Standard (Default)
· Advanced
In/Out
Settings
Output
Voltage *
Check the output voltage.
Output Voltage:
100 V (Fixed)
Standard
AC I/P
Sensitivity *
Set the input sensitivity.
(Note 1)
AC I/P Sensitivity:
· Normal (Default)
· Low,
· High
Input Plug * Set this when replacing the
input plug.
Input Plug:
15A, 20A, 30A, Hard wire/50A
(dependent on the UPS model)
(Default: BN50T / BN75T / BN100T /
BN150T: 15A,
BN220T / BN300T:30A
ECO Mode * Set whether to enable ECO
Mode.
ECO mode:
· Disable (Default)
· Enable
Advanced
Frequency
Range *
Switch the frequency range
mode.
Frequency Range:
· Normal Range (Default)
· Wide Range
Transfer
Sensitivity *
Set the sensitivity at which to
switch to Battery Mode.
Transfer Sensitivity:
· Normal (Default)
· High
Boot
Settings
Auto Reboot Set auto restart from power
failure.
Auto Reboot:
· Enable (Default)
· Disable
Standard
Cold Start
Set whether to enable the cold
start function that can start up
the UPS even when there is no
AC input.
Cold Start:
· Enable (Default)
· Disable
Reboot
Delay Time
Set the delay time for recovery
from power failure.
Reboot Delay Time:
0 to 999sec.(Default: 9sec)
Advanced
Load
Segments
Set this when you want the
delay time for restarting re-
ceptacle group B and C to be
longer than that for group A.
Load Segments:
ON delay Out B: 0 to 1800s
ON delay Out C: 0 to :0 to 1800s
OFF delay Out B: 0 to 1800s
OFF delay Out C: 0 to 1800s
(Default: above all 0s)
Reboot
Batt.level
Set the amount of battery
charge for restarting the UPS.
Reboot Batt.level:
0 to 100%(Default: 0%)
Auto Reboot
Mode
Set the mode for rebooting.
Auto Reboot Mode:
· Mode A (Default)
· Mode B
Power SW
OFF Mode
Switch the operating mode of
the power switch.
Power SW OFF Mode:
· UPS shutdown (Default),
· UPS+PC Shutdown
Summary of Contents for BN100T
Page 2: ......
Page 24: ...1 Preparation BN50T BN75T BN100T BN150T BN220T BN300T 1 8...
Page 36: ...2 Installation and connection BN50T BN75T BN100T BN150T BN220T BN300T 2 12...
Page 54: ...3 Check and start operation BN50T BN75T BN100T BN150T BN220T BN300T 3 18...
Page 72: ...4 Maintenance and Inspection BN50T BN75T BN100T BN150T BN220T BN300T 4 18...
Page 88: ...6 Using the contact signal functions BN50T BN75T BN100T BN150T BN220T BN300T 6 8...
Page 94: ...8 Troubleshooting BN50T BN75T BN100T BN150T BN220T BN300T 8 4...
Page 96: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 2 2 FA OA 2 AC 50 60Hz AC AC...
Page 97: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 9 3 AC AC 3P 2P AC AC 5cm UPS UPS...
Page 99: ...9 Note of Chinese BN50T BN75T BN100T BN150T BN220T BN300T 9 9 5 1mA AC UPS AC UPS...
Page 109: ...Cut here...