79
Master Parameter Editing Details (Tab Descriptions)
Section 4-7
Note a) If the I/O size of the device displayed in the Network Configuration
Window does not coincide with the I/O data size of the device reg-
istered with the scan list, the following warning dialog will be dis-
played along with the Edit Device Parameters Window. In this
case, the I/O size in the scan list will take priority.
If an EDS file has not been installed in the slave, obtain the EDS
file and install it. Also, set the correct I/O size in all slaves that re-
quire changes in the I/O size.
b) If the slave device registered with the scan list has already been
registered with another master, the following warning will be dis-
played along with the Edit Device Parameters Window.
Revise the slaves registered in the scan list.
4-7-1
Edit Device Parameters on CS1W-DRM21/CJ1W-DRM21
Note
When the CS1W-DRM21/CJ1W-DRM21 DeviceNet Unit is used, select the
device and then select
Device
, and
Property
and turn ON
Enable Master
Function
in the Properties Dialog Box.