151
Error History Information
Appendix C
0101
No transmission is possible because the Master
node is not in the network.
FINS message communications
Command
Bit 15: OFF
Bit 14 to 8: SNA
Bit 7 to 0: SA1
Response
Bit 15: ON
Bit 14 to 8: DNA
Bit 7 to 0: DA1
Explicit message transmission
Command
Bit 15: OFF
Bit 14 to 8: 0
Bit 7: ON
Bit 6 to 0: Master node address
Response
Bit 15: ON
Bit 14 to 8: 0
Bit 7: ON
Bit 6 to 0: Master node address
No
0105
No transmission is possible because the node
address setting is wrong.
No
0106
No transmission is possible because the node
address is duplicated.
No
0107
No transmission is possible because the destination
node is not in the network.
No
0108
No transmission is possible because there is no Unit
corresponding to the unit number.
No
0109
No transmission is possible because the destination
node is busy.
No
010B
No transmission is possible because the CPU Unit
has an error
No
010D
No transmission is possible because the destination
address is not registered in the routing table.
No
010E
No transmission is possible because the routing
tables are not registered.
FINS message communications
Command
Bit 15: OFF
Bit 14 to 8: SNA
Bit 7 to 0: SA1
Response
Bit 15: ON
Bit 14 to 8: DNA
Bit 7 to 0: DA1
Explicit message transmission
Command
Bit 15: OFF
Bit 14 to 8: 0
Bit 7: ON
Bit 6 to 0: Master node address
Response
Bit 15: ON
Bit 14 to 8: 0
Bit 7: ON
Bit 6 to 0: Master node address
No
010F
No transmission was possible because the routing
tables are wrong.
No
0110
No transmission was possible because the number
of relay times is excessive.
No
0111
No transmission is possible because the command
is in excess of the maximum permissible command
length.
No
0112
No transmission is possible because the header is
wrong.
No
0117
The packet was discarded because the internal
reception buffer was full.
No
0118
The packet was illegal and discarded.
No
0120
An unexpected routing error.
FINS message communication
Command
Bit 15: OFF
Bit 14 to 8: SNA
Bit 7 to 0: SA1
Response
Bit 15: ON
Bit 14 to 8: DNA
Bit 7 to 0: DA1
Explicit message communication
Command
Bit 15: OFF
Bit 14 to 8: 0
Bit 7: ON
Bit 6 to 0: Master node address
Response
Bit 15: ON
Bit 14 to 8: 0
Bit 7: ON
Bit 6 to 0: Master node address
No
0123
The packet was discarded because the internal
transmission buffer was full.
No
0124
Routing failed because the frame length was in
excess of the maximum permissible length.
No
0125
The packet was discarded due to a response time-
out error.
No
Error
code
(Hex)
Error Error
data
EEPROM
Upper 2 digits
Lower 2 digits
Summary of Contents for 3G8E2-DRM21-EV1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x ...
Page 13: ...xiv ...
Page 19: ......
Page 33: ...14 Operating Environment Section 1 3 ...
Page 145: ......
Page 161: ......
Page 165: ......
Page 167: ......
Page 173: ......
Page 175: ......
Page 177: ......
Page 179: ......
Page 181: ......
Page 187: ......