50
Connecting to the Network
Section 3-3
Baud Rate
Select the baud rate for the serial communications port of the CS/CJ-series
PLC from the following settings.
• 9,600 bps, 19,200 bps, 38,400 bps, or 115,200 bps
Note The Tool bus and Host Link are different to each other in available
baud rate. For details, refer to the
CS/CJ Operation Manual
.
Data Length
Select the data length for the serial communications port of the CS/CJ-series
PLC from the following settings if Host Link is used.
• 8 or 7 bits
Parity
Select the parity for the serial communications port of the CS/CJ-series PLC
from the following settings if Host Link is used.
• None, even, or odd
Stop Bits
Set the number of stop bits for the serial communications port of the CS/CJ-
series PLC from the following settings if Host Link is used.
• 1 bit or 2 bits
5.
Click the
OK
Button.
A confirmation window will appear. Click the
OK
Button. The Configurator
will be connected to the DeviceNet network. When the Configurator is con-
nected online, the color of the status indicator on the status bar will change
to blue and
Online
will be displayed.
Note
When using a CS1W-CN226/626 or XW2Z-200S-CV/500S-CV Connecting
Cable to make a serial connection to a CS-series CPU Rack containing a
CS1W-DRM21, Host Link is selectable as the interface, but connection will not
be possible if it is selected. In this case, select
Toolbus
.
However, when using an XW2Z-200S-CV/500S-CV Connecting Cable or
CS1W-CN114 + CQM1-CIF02, connection is possible by selecting Host Link
as the interface.
Note
When Host Link is selected, it may take several minutes to download from the
network. Selecting
Toolbus
is therefore recommended for serial connections.
Selecting SYSMAC CS/CJ
Ethernet Unit IF
The Configurator can be connected directly to the DeviceNet network via
Ethernet through a CS/CJ-series Ethernet Unit and a CS/CJ-series DeviceNet
Unit.
Note
The Ethernet connection can be made only with the CS/CJ-series Ethernet
Unit and CS/CJ-series DeviceNet Unit combination. Connection by the combi-
nation of other PLC-series Units is not possible.
WS02-CFDC1-E
Configurator
CS-series
DeviceNet Unit
DeviceNet network
When using a CS1W-CN226/
626 or XW2Z-200S-CV/500S-
CV Connecting Cable, Host Link
cannot be used. Select Toolbus.
Summary of Contents for 3G8E2-DRM21-EV1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x ...
Page 13: ...xiv ...
Page 19: ......
Page 33: ...14 Operating Environment Section 1 3 ...
Page 145: ......
Page 161: ......
Page 165: ......
Page 167: ......
Page 173: ......
Page 175: ......
Page 177: ......
Page 179: ......
Page 181: ......
Page 187: ......