86
Manual I/O Allocations
Section 4-8
Example:
3300:Bit00: Starts with bit 00 (LSB) of word 3300.
3300:Bit08: Starts with bit 08 (MSB) of word 3300.
No words in the CPU Unit will be displayed for any memory block that is
not in use.
4-8-2
Changing the First Address of Output/Input Block
Device - Parameter - Edit - I/O Allocation Tab - Setup Button
To change the output/input block allocation areas in the I/O memory of the
CPU Unit, use the following procedure.
1,2,3...
1.
Click the
Setup
Button of the block to be changed.
2.
The following window will be displayed.
3.
Set the area, start word, and the number of words for the block.
The number of words to be displayed in a block by the Configurator is set
in the Words field. For the CS1W-DRM21 or CJ1W-DRM21, the maximum
number of words that can be allocated to one block is 500. For the
C200HW-DRM21-V1 and CVM1-DRM21-V1, the maximum number of
words that can be allocated to one block is 100.
The ranges that can be set are shown below.
•
CS1W-DRM21 or CJ1W-DRM21
Banks 0 to 12 of the EM area can be used.
Word address (Example 3300)
First bit address (Bit00)
Example: Allocation starts with
bit 00 (LSB) of word 3300.
Product name of slave
Allocated the bytes beginning with bit 08
of word 3300. Therefore, the product
name for 3300:Bit08 is left blank.
PLC model
Data area
Range
CS Series or
CJ Series
CIO Area
0000 to 6143
DM Area
DM 0000 to DM 8191
Work Area
WR 000 to WR 511
HR Area
HR 000 to HR 511
EM Area
EM 00000 to EM 32767
Summary of Contents for 3G8E2-DRM21-EV1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x ...
Page 13: ...xiv ...
Page 19: ......
Page 33: ...14 Operating Environment Section 1 3 ...
Page 145: ......
Page 161: ......
Page 165: ......
Page 167: ......
Page 173: ......
Page 175: ......
Page 177: ......
Page 179: ......
Page 181: ......
Page 187: ......