54
Connecting to the Network
Section 3-3
Registration of the connection Dialog Box
Setting the Network Address in Host (PLC) Information:
Set the FINS network address for the computer. The computer running the
Configurator uses OMRON’s FINS communications service to connect to the
DeviceNet network via Ethernet. Thus, the computer must have not only an IP
address, but also a FINS network address and node address. The relation-
ship between the FINS node address and the IP address is specified by the
address conversion in the Ethernet Unit.
Obtain the FINS node address corresponding to the IP address (See note.) of
the computer from the address conversion of the Ethernet Unit. Refer to
Infor-
mation on Address Conversion
on page 56 for details.
Setting the Node Address in Host (PLC) Information:
Set the FINS node address for the computer.
Obtain the FINS node address corresponding to the IP address (See note.) of
the computer from the address conversion of the Ethernet Unit. Refer to
Infor-
mation on Address Conversion
on page 56 for details.
Registration
Name
The registration name for the DeviceNet network to be connected is
set here. Up to 20 networks can be set, each up to 25 characters in
length.
Host (PLC)
Information
This is the setting for the Configurator computer.
Network
Address
The user inputs the FINS network address for the
computer here. Set the same address as the one set
for the Ethernet Unit. Input 0 if no other address is
going to be set.
Node address The user inputs the FINS node address for the com-
puter here.
Remote Infor-
mation
These are the settings for the DeviceNet Unit and Ethernet Unit that
are used to connect with the DeviceNet network.
DeviceNet
Unit
Network
Address
Input the FINS network address for
the DeviceNet to be connected.
Input if crossing networks past
the direct Ethernet connection. If
not crossing networks, input 0.
Node Address Input the node address for the
DeviceNet to be connected.
Input if
crossing networks past the
direct Ethernet connection. If not
crossing networks, input 0.
Unit No.
Input the unit No. of the DeviceNet
to be connected, for use as a CPU
Bus Unit.
Ethernet Unit
Port No.
Input the Fins UDP port No. for the
Ethernet Unit.
IP Address
Input the IP address for the Ethernet
Unit.
Summary of Contents for 3G8E2-DRM21-EV1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x ...
Page 13: ...xiv ...
Page 19: ......
Page 33: ...14 Operating Environment Section 1 3 ...
Page 145: ......
Page 161: ......
Page 165: ......
Page 167: ......
Page 173: ......
Page 175: ......
Page 177: ......
Page 179: ......
Page 181: ......
Page 187: ......