43
Hot water
1” internal thread
max. operating pressure DHW side
87 PSI
max. operating pressure heating water side
43.5 PSI
max. accumulator temperature
230°F
min. accumulator temperature
140°F at a set hot water temperature 122°F
Thermostat
adjustable from 68°F – 140°F
Pump data
Charge pump
220V, 60Hz, Wilo Yonos Para RS 25/6
Power consumption
3 – 45 Watt
Current consumption
0,028 —0,44 A
Information regarding the corrosive effect of water on soldered plate heat exchangers
The soldered plate heat exchanger is made from stainless steel 316 or 304 and copper solder. In this case, the
resistance of both stainless steel and copper must be considered. Particular attention must be paid to compli-
ance with the values in the following table. In addition, mixed installations (especially with galvanized pipes)
must be avoided.
pH value
7 – 9
Free chlorine
< 0,5 ppm
SO
4
⁻⁻⁻
< 100 ppm
Fe
+++
< 0,5 ppm
HC0
3
⁻
/ SO
4
⁻⁻
> 1
Mn
+++
< 0,05 ppm
Cl
⁻
< 50 ppm
CO
2
< 10 ppm
PO
4
⁻⁻
< 2 ppm
H
2
S
< 50 ppb
NH
3
< 0,5 ppm
Conductivity
> 50
µ
S/cm, < 600
µ
S/cm
Wall temperature
< 149° F
Oxygen
< 0,1 ppm
Total hardness
4,0 bis 8,5 °dH
All specified details are for information only and cannot be used as a basis for warranty claims. To prevent pit-
ting below coverings, all types of incrustation and contamination must be avoided in the heat exchanger. Fur-
thermore, the water flow rate and contamination with S0
2
and iron are relevant. The redox potential of the
solution (a function of the oxidising compounds, such as oxygen, hypochlorous acid and sodium carbonate)
must also be observed. In practice, the fresh water module shows up to a value of 15 ° d hardness high resis-
tance to calcification. At higher values, a decalcification plant can reduce the maintenance interval
significantly!
Installation Manual PELLEMATIC® SmartXS
Summary of Contents for PELLEMATIC SmartXS
Page 29: ...Dismantling of the housing parts 29 Installation Manual PELLEMATIC SmartXS ...
Page 30: ...PE 607 USA_FA 2 1 30 Dismantling of the housing parts ...
Page 45: ...Suggested piping arrangement for combined operation 45 Installation Manual PELLEMATIC SmartXS ...
Page 49: ...Wiring diagrams 49 Installation Manual PELLEMATIC SmartXS ...
Page 50: ...PE 607 USA_FA 2 1 50 Wiring diagrams ...
Page 51: ...Wiring diagrams 51 Installation Manual PELLEMATIC SmartXS ...
Page 52: ...PE 607 USA_FA 2 1 52 Wiring diagrams ...
Page 96: ...PE 607 USA_FA 2 1 96 Pellet boiler cautionary markings ...
Page 97: ...Pellet boiler cautionary markings 97 Installation Manual PELLEMATIC SmartXS ...
Page 98: ......
Page 99: ......