Cause and Remedy:
Sensor defect
►
Measure sensor (approx. 5 mV at 125°C) replace if
required
Sensor cable defect
►
Replace sensor
Sensor temperature too
low
►
Sensor temperature below measuring range (– 10°
C)
Sensor polarity reversed
►
Change sensor conn and –
13.5 Underpressure box (Fault 5012, 5013, 5041, 5042)
Display:
[5012] PE Underpressure box BS
Description:
Negative draft input open, measuring circuit from negative draft measurement
open – Input UP
Cause and Remedy:
Signal incorrect
►
Check poarity and signal (0-10V)
Signal cable defect
►
Replace sensor
No signal
►
Replace underpressure box
Combustion chamber leak
►
Check total closure of boiler door
PE 607 USA_FA 2.1
78