Technical data PELLEMATIC SmartXS
93
18
Technical data PELLEMATIC SmartXS
Designation
UOM
SmartXS
Boiler power full load
kW
20
Boiler Power Minimum
kW
6
Efficiency Condensing Mode
%
93.9
Efficiency Non-Condensing Mode
%
88.9
Rated AFUE
%
Boiler Water Temperature
°F
83 to 194 (when controlled by
outside temperature)
Minimum Boiler Temperature
°F
83
Minimum Return Temperature
°F
41
Combustuion Chamber Temperature
°F
752 to 1652
Water area
Maximum Operation Pressure
P.S.I.
43.5
Water Capacity
Gal.
88.5
Cleaning water connection
In.
3/4
Supply and Return connections
In.
1" female with gasket
DHW connection
In.
3/4
Head Pressure across boiler @ 18°F Delta
In. W.C.
8.6
Head Pressure across boiler @ 36°F Delta
In. W.C.
2.3
DHW Heat Exchanger volume
Gal.
0.25
Solar Heat Exchanger voulme (optional)
Gal.
0.2
DHW Max volume @ operating point A
Gal.
/Min.
5.55
Operating Point A DHW inlet temperature
°F
50 to 113
Operating Point A DHW outlet temperature
°F
140
Maximum Pressure for DHW Section
P.S.I.
87
Maximum Pressure for Solar Heat Exchanger
P.S.I.
87
Flue Gas Section
Temperature Maximum Condensing
°F
104 - 176
Temperature Minimum Condensing
°F
104 - 176
Temperature Maximum Non-Condensing
°F
140 - 194
Temperature Minimum Non-Condensing
°F
140 - 194
Flue Gas Pipe diameter @ Boiler
In.
5.19
Flue Pipe Connection Point Height
In.
17.5
Condensate Drain Height
In.
9
Chimney Diameter/ Area Minimum
Sq. In.
19.6 (5 In. Diameter)
Chimney Construction
Qualified for condensing
conditions, damp resistant, N1 or
P1 pressure sealed depending on
chimney calculation.
Installation Manual PELLEMATIC® SmartXS
Summary of Contents for PELLEMATIC SmartXS
Page 29: ...Dismantling of the housing parts 29 Installation Manual PELLEMATIC SmartXS ...
Page 30: ...PE 607 USA_FA 2 1 30 Dismantling of the housing parts ...
Page 45: ...Suggested piping arrangement for combined operation 45 Installation Manual PELLEMATIC SmartXS ...
Page 49: ...Wiring diagrams 49 Installation Manual PELLEMATIC SmartXS ...
Page 50: ...PE 607 USA_FA 2 1 50 Wiring diagrams ...
Page 51: ...Wiring diagrams 51 Installation Manual PELLEMATIC SmartXS ...
Page 52: ...PE 607 USA_FA 2 1 52 Wiring diagrams ...
Page 96: ...PE 607 USA_FA 2 1 96 Pellet boiler cautionary markings ...
Page 97: ...Pellet boiler cautionary markings 97 Installation Manual PELLEMATIC SmartXS ...
Page 98: ......
Page 99: ......