87
Exhaust Vent. Type
EC
FRT Controller
Mode
On
Min Temp
248° F
Set ++
0 K
Limit Upper
30%
Limit Lower
80%
PID Gain
4%
PID Integration Time
200 sec
PID Different Time
2 zs
Weight System
Mode
Textile
Tank
Threshold
882 lB.
Correction Value
0 lB.
Boiler Control Pump
On Temp
95° F
Depends on Require
Dependent
Pumptype
Energy
efficient
minimum speed
10 %
maximum speed
100 %
Switch Off Hyst
3 K
Run Down Time
15 min
Control Range
10 K
Suction Turbine
Cleaning / Filling
19:00
Cleaning 2
Off
Pulse RA Motor
60 sec
Pause RA Motor
0 sec
Suction Interval
180 min
Cleaning
Mode
On
Cleaning Time
60 sec
Maintenance
Mode
Off
Interval
12 months
Burner Run Time
Off
Interval
1000 h
Calibrate
Mode
Off
Installation Manual PELLEMATIC® SmartXS
Summary of Contents for PELLEMATIC SmartXS
Page 29: ...Dismantling of the housing parts 29 Installation Manual PELLEMATIC SmartXS ...
Page 30: ...PE 607 USA_FA 2 1 30 Dismantling of the housing parts ...
Page 45: ...Suggested piping arrangement for combined operation 45 Installation Manual PELLEMATIC SmartXS ...
Page 49: ...Wiring diagrams 49 Installation Manual PELLEMATIC SmartXS ...
Page 50: ...PE 607 USA_FA 2 1 50 Wiring diagrams ...
Page 51: ...Wiring diagrams 51 Installation Manual PELLEMATIC SmartXS ...
Page 52: ...PE 607 USA_FA 2 1 52 Wiring diagrams ...
Page 96: ...PE 607 USA_FA 2 1 96 Pellet boiler cautionary markings ...
Page 97: ...Pellet boiler cautionary markings 97 Installation Manual PELLEMATIC SmartXS ...
Page 98: ......
Page 99: ......