14.1.3 Output Test
The Output Test serves to check all connected
outputs:
• all motors
• relay fault signals
• magnet valves
• boiler controlled pumps
Note:
After choosing of one port, the operation will
be interrupted.
By leaving the menu
output test
the normal
operation will continue.
The output test is designed to test all outputs connected to the system (e.g. all motors, the alarm signal re-
lay, the solenoid valve and the recirculation pump).
By using the operative device and typing in the code, you can access the item
output test
in the menu
general
.
You can control the required output with ON / OFF and choose the power input 0 -100%.
Designation
Check if
If not, then check
Motor suction fan
VAK
the suction fan on the hopper is
running
• the suction fan is connected
• the fuse is defective
• the motor is defective
Ignition
ZUEND
the electrode is working: you can view
the current draw at the control unit af-
ter it has been switched on.
• the wiring is correct
• Check the ignition electrode
Motor hopper
RES 1
The hopper motor is running.
• the wiring is correct
• the motor is defective
Solenoid valve
RM
the solenoid valve switches over and
you can hear it click
Note:
Low temperature systems only
• the scrubber is connected
• the scrubber is defective
Fault signal relay
SM
the relay switches on and off: you can
hear it clicking on and off
• the wiring is correct
• the fault signal relay is defective
Flue gas fan
SZ
the flue gas fan is running
• the wiring is correct
• the motor is defective
Heating circuit
pump
UW
the heating circuit pump is running
Note:
only possible if the heating circuit
pump is connected
• the wiring is correct
• the Heating circuit pump is defective
PE 607 USA_FA 2.1
68
Summary of Contents for PELLEMATIC SmartXS
Page 29: ...Dismantling of the housing parts 29 Installation Manual PELLEMATIC SmartXS ...
Page 30: ...PE 607 USA_FA 2 1 30 Dismantling of the housing parts ...
Page 45: ...Suggested piping arrangement for combined operation 45 Installation Manual PELLEMATIC SmartXS ...
Page 49: ...Wiring diagrams 49 Installation Manual PELLEMATIC SmartXS ...
Page 50: ...PE 607 USA_FA 2 1 50 Wiring diagrams ...
Page 51: ...Wiring diagrams 51 Installation Manual PELLEMATIC SmartXS ...
Page 52: ...PE 607 USA_FA 2 1 52 Wiring diagrams ...
Page 96: ...PE 607 USA_FA 2 1 96 Pellet boiler cautionary markings ...
Page 97: ...Pellet boiler cautionary markings 97 Installation Manual PELLEMATIC SmartXS ...
Page 98: ......
Page 99: ......