OPERATION
7. HOW TO USE BASIC FUNCTION
7-5-4. Sets the Origin Point
This setting is for matching the values of the machine position and current position on VARICAM's display when the
machine position is on the origin point (0 degree).
Sets the “origin point setting” according to the following procedures.
[ 1 ] Moves the machine to the origin point position.
[ 2 ] Checks that VARICAM and ABSOCODER are connected.
If VARICAM and ABSOCODER are not connected, VARICAM will detect the sensor error (u08). Therefore, the
origin point is impossible to set.
[ 3 ] Sets the parameter by the following procedures.
①
Selects the parameter No. 99.
Selects “99” by pressing [+] or [-] key of SW / PRM.
②
Designates the origin point.
Presses [SET] key, and then “000” blinks on
the POSITION display area for the confirmation.
If [CLR] key is pressed in this timing, the “origin point
setting” will be canceled.
Presses [SET] key again, and then “000” turns ON.
The “origin point setting” is completed.
Presses [SET] key once, the numeric value blinks.
Presses it again, the numeric value turns ON.