gave a response to confirm the activation. (Input
“TD response” in the wiring diagrams can be used for
this confirmation signal).
red LED "Call Fire Brigade“
Indicates that the FCP is in Main Alarm condition but the
alarm transmission device (TD) could not be activated.
So the Fire Brigade maybe has to be called by phone.
yellow LED "Fault“
Indicates that the FCP is in fault condition. At least one
device (detector, module), input, output or system
component is not in normal condition. See LC module for
detailed information.
yellow LED "System“
The FCP itself is in fault condition. That means that
maybe the main board (micro controller) does not
work well and the correct function of the FCP is not
guaranteed. Please check immediately by the
installation company.
yellow LED "Disabling“
Indicates that at least one device (detector, module),
input or output is disabled (switched off).
yellow LED "Transmission Device“ (TD)
In case of flashing this LED (and yellow LED "Fault“ is
on) the TD is in fault condition.
In case this LED is on (and yellow LED "Disabled“ is on)
the TD is switched off.
yellow LED "Sounders“
In case of flashing this LED (and yellow LED "Fault“ is
on) one of the sounder outputs is in fault condition.
In case this LED is on (and yellow LED "Disabled“ is on)
one of the sounder outputs is switched off.
red LED "FPE activated“
One or more automatic controlling, configured to
switching function "switch like fire protection equipment“,
are active.
LC module indications:
The LC module is a graphics LCD which is automatically illuminated in the case of any event. That means
if an alarm message, a fault message, a disabled message or just if any push button is pressed the LC
module activated the illumination. Then detailed information is shown in the display. Either the LCD
shows the information in 8 lines of alpha numerical texts or in a graphics mode like bar charts or columns.
Usually the FCP shows the condition of the panel in the middle of the LC module. There is in big letter the
current status on a dark background. The following messages are possible :
IN OPERATION
= normal condition
ALARM
= the FCP is in alarm condition
T E S T ALARM
= the FCP is in test alarm condition
FAULT
= the FCP is in fault condition
SWITCH OFF
= certain devices of the FCP are switched off
ACTIVATION
= outputs are activated by automatic controllings
If the user enters one of the menus (by pressing the push button „Prog“) at the bottom line of the LC
module he sees the dynamic function keys F1 – F4. Sometimes all 4 keys are used, sometimes only