NSC Sicherheitstechnik GmbH
41/47
2011 / 04 / 26
Eckendorfer Str. 125 c
Installation Manual Solution F2 20110509.doc
33609 Bielefeld
Version S031A01.01
Checking the end of line resistor on the RS485 bus
End of line resistor activated at first and last device (jumper matched)?
Ο
o.k.
Ο
fault
Commissioning of the power supply
- plug 230VAC mains cable or check already plugged cable!
- switch on power supply for fire control panel!
The internal buzzer will be on: please switch off by pressing
Scanning of internal an external components
Detector modules
After scanning process and uploading of the programming out of the flash memory all recognised
components will be displayed in a list.
Exampel:
Hardware modules
1. Loop module HOCHIKI ESP : 02
2. Loop module Apollo XP/DISCOV: 00
3. Conventional detector module: 00
4. Input-/output extension : 00
↓
Cancel Details
Number of mounted detector modules correctly recognised?
Ο
o.k.
Ο
fault
By pressing the "Details“ key F3 the addresses of the modules can be checked.
Exampel:
Hardware modules 01/02
>01 Detector module HOCHIKI ESP
02 Detector module HOCHIKI ESP
Cancel Details