Test mode
1. Detector test
2. Manual Control
3. Simulation
4. Revision
Cancel Enter
Main menu: Test functions
As soon as this menu is selected the FCP is in the
service mode. This will be indicated by the yellow
LED „Service“. After leaving this menu the LED is
off.
1. The function„Detector test can be used to
set individual detectors in alarm condition
(electronically)
Jump to Menu
23
2. Manual Control means manual controlling
of the outputs. With a simple press on a
push button an output can be activated
Jump to Menu
24
3. Simulation can be used to set individual
detectors in alarm condition without
connected detectors (by software). This is
useful for testing the panel outputs /
indications as long as the panel is not
installed
Jump to Menu
25
4. Revision means a „One-Man-Test
procedure“ to set smoke and heat detectors
in alarm by using special test equipment.
During this procedure the FCP resets all
alarms on the relevant zones automatically
after a certain time
Jump to Menu
26
23
Detector test Status
Zone : 2 Normal
Detector : 3 Normal
Alarm unset (outputs inactive) !
Cancel On set
Example of detector test :
Detector not yet in alarm :
0002/002 opt. det. ALG-
Evt. individual detector text
A-Value
████████
0,0%/m
Pre alarm
███████████████
2,7%/m
Alarm
█████████████████
3,4%/m
Cancel Calib. Details
Detector in alarm :
0002/002 opt. det. ALG-E
Evt. individual detector text
A-Value
██████████████████████
4,5%/m
Pre alarm
███████████████
2,7%/m
Alarm
█████████████████
3,4%/m
Cancel Calib. Details
Detector test (only for addressable
detectors)
First zone and detector number (within the zone) has
to be typed. Every line has to be confirmed by “OK”.
The push button F4 („set / unset“) can be used to
configure if the outputs of the FCP shall be activated
during the test alarm or not. The current selection is
displayed in the last but one line of the LC module
(here : „outputs inactive“).
After that the test alarm can be activated by pressing
F2 („On“).
By using the „System Settings“ (parameter 16) it is
possible to configure an auto-reset of the test alarm
condition or no auto-reset. In that case the test alarm
has to be reset by pressing „Reset“
.
The bar charts as in the example on the left side show
how the test alarm will arise (see A-value). If the
analogue value passes the alarm threshold the
detector goes into alarm condition.