Also all loopsounders belong to the external
sounders.
comes in the sounders / strobes will not be
activated again until they are switched on again.
02.7
Switch on/off
1. Zones & detect. 5. Sounder/Strobe
2. Output 6. Alarm Trans.Dev.
3. Relay 7. Delay
4. Power Output 8. Fire Outputs
Cancel off
"Transmission devices" are all power outputs, relays
and outputs, which are configured to switching
function „on/off like transmission device“.
Switching on/off: Alarm Transmission Device
(TD)
After selecting this function in the switch on/off main
menu you see at the bottom line of the LCD "off“
(F3) or "on“ (F2).
By pressing F3 the Alarm transmission device will be
switched off continuously.
The current status of the TD will additionally
indicated by the yellow LED on the control panel.
02.8
Switch on/off
1. Zones & detect. 5. Sounder/Strobe
2. Output 6. Alarm Trans.Dev.
3. Relay 7. Delay
4. Power Output 8. Fire Outputs
Cancel on
Switching on/off: Alarm transmission delay
Here the delay of the alarm transmission device of the
FCP „Solution F2” can be switched on/off.
After selecting this function you see at the bottom line
of the LCD "off“ (F3) or "on“ (F2). “On” means to
activate the delay (Day Mode)
The current status of the delay will be additionally
indicated by the green LEDs (Delay, No Delay) on
the control panel.
When the delay is activated there is an additional
indication in the LC module (“Delay activated”)
Pay attention :
To switch on the delay of the alarm transmission
device is only possible if “Response time” and
“Inspection time” are configured. This can only be
done by the installer company.
02.9
Switch on/off
1. Zones & detect. 5. Sounder/Strobe
2. Output 6. Alarm Trans.Dev.
3. Relay 7. Delay
4. Power Output 8. Fire Outputs
Cancel off
Switching on/off: Fire protection outputs
This function disables all outputs which have been
configured to "switch on/off like fire protection
outputs".
This disablement only is possible in case of no
alarm.
After selecting this function you see at the bottom line
of the LCD "off“ (F3) or "on“ (F2).
Pay attention :
By the function (F3) all fire outputs will be switched
off continuously. If an alarm comes in no output will
be activated.
03
Alarmcounter
FCP - Alarm : 0025
Testalarm : 0011
cancel
Alarmcounter
It is a 4 digit number (1 – 9999).
Testalarms (Detector test/revision) will be displayed
by a seperate counter.