NSC Sicherheitstechnik GmbH
16/47
2011 / 04 / 26
Eckendorfer Str. 125 c
Installation Manual Solution F2 20110509.doc
33609 Bielefeld
Version S031A01.01
MCP XP95
Manual Call Point
Sounderm. XP95
Sounder output module
Inp.mod. XP95
Input module
Zone mod. XP95
Conventional module
Inp/Outp. XP95
Input-/output module
Flame det. XP95
Flame detector
Beam XP95
Beam detector
Ref.Beam XP95
Beam detector with
reflector
opt. det. XPlorer
Optical smoke detector
Heat det. XPlorer
Heat detector
H.Thermo. XPlorer
Heat detector high
temperatur
opt. det. S90
Optical smoke detector
Ion. det. S90
Ionisation smoke detect.
Heat det. S90
Heat detector
MCP S90
Manual Call Point
Inp.mod. S90
Input module
Inp/Outp. S90
Input-/output module
Sounderm. S90
Sounder output module
Seg. : Segment = Section of addresses with a
maximum of 254 Hochiki detectors,
modules / base sounders and a maximum
of 126 Apollo detectors, modules.
The segments are partitioned according this list :
•
Loop 1 Main board: Segment 1
•
Loop 2 Loop extension: Segment 2
o
: This is a symbol for a loop.
-
: This is a symbol for a stub line.
Adr. : Detector address (physical address stored
in the detector)
Status : Current status of the detector (e.g. normal
condition, alarm condition, fault condition,
disabled condition)
By pressing F4 („Details“) it is possible to display
more details of the detectors. That means analogue
values, dust contamination, input bits and so on.
.
Jump to Picture
07.2
for Manual Call Points
Jump to Picture
07.3
for optical smoke detector
07.2
0001/001 MCP CHQ-CP
Configured detector text
1 2 3 4 5 6 7 8
Inputs |0| | | | | | | |
Outputs |0| | | | | | | |
Fault : missing
Cancel
Example of detector data: MCP
The input bits display the status of the alarm contact
of the MCP or - in case of input modules - the status
of the input bits of the module (high / low).
The “Output” bits show – in case of output modules –
which outputs are active or in fault condition.
Following status are possible:
•
0 = inactive
•
1 = active
•
x = reset
•
= open curcuit
•
S = short curcuit
•
U = undefined
The last but one line shows any additional fault
information if the detector/module is not in normal
condition (here: fault because detector is missing).