NSC Sicherheitstechnik GmbH
20/47
2011 / 04 / 26
Eckendorfer Str. 125 c
Installation Manual Solution F2 20110509.doc
33609 Bielefeld
Version S031A01.01
•
CONNECT 33600 (Connection to other modem
established)
•
NO CARRIER (Connection terminated)
You can cancel a connection by pressing F3 „hang
up“.
08.4
Internal Modules 01/63
>01 FRP with FBC A B
02 Remote LCD Panel A
03 Remote LCD Panel A
04 FRP A B
05 -
06 -
Cancel Details
Display of FRP/LCD Panel
Different protocol can be set to each serial interface
of the FCP. (s. menu 38.1).
On all interfaces set to "FRP protocol" connected
devices will be scanned. The address range for these
devices is 1-63.
The device types will be shown as text.
Folowing devices are available:
FRP
FRP with FBC
Remote LCD Panel
LED Panel
PC Managementsystem
By characters "A" and "B" will be signalised, on which
channels a device has been connected.
For further informations please press „Details“ (F4)
jump to menu
8.5
08.5
FRP with FBC
Softwareversion : S150A01.01
24V 1 : OK
24V 2 : Fault
FBC : OK
Checksum : OK
Restart : OK
zurück
Example of details of a fire brigade repeater
panel with fire brigade control panel
In case of a fault of a RS485 device this menu
gives a hint about fault reason. In this example
24V supply voltage on input 2 of the FRP is
missing.
09
Voltages
Charging voltage nominal: 27,66 V
Charging voltage actual : 27,57 V
Battery voltage : 27,48 V
Earth fault voltage : 1,42 V
Ri-Battery : 00,55 Ohm
Cancel
Example of power supply voltages
The charging voltage should be in between 27,3V and
27,6V (20°C). This should be checked by voltage
meter.
The earth fault voltage normally has a value between
9 V and 17,5V. In case of an earth fault you can see
here, i fit is an earth fault against plus oder minus
potential.
Mit F1 ("zurück") Rücksprung aus dem Menü.
10
Power outputs
No.: Vot. Th.SC R-Act. Th.OC(Cal.)
1 : 2,42V 0741< 1008 <1108 (1008)Ohm
2 : 2,39V 0734< 1000 <1095 (0995)Ohm
3 : 4,70V 0838< 1958
>
1383 (1283)Ohm
4 : 0,02V 0975
>
0008 <1475 (1375)Ohm
cancel
Example of power output voltages
The voltage and the measured resistance for each
power output will be displayed, furthermore the
thresolds for open- and shortcircuit.
The samploe on the left side shows an open circuit
for line 3 and an short circuit for line 4.
Leaving the menu by pressing F1 („Cancel“).