Reset 1st alarm has influence in case of cross
detection or cross zoning. The 1st will be reset
automativally after the configured time elapsed,but
only if no further alarm has raised in this time.
only with FBC
Switzerland
(s. Parameter 1)
0-60
Minutes
05
Fault reset
0
Automatically
1
by „
“
06
Fault remind
0-30
Minutes or 0=no
remind
07
Summer time
switching
0
Automatically
1
Off
08
Detector LED
flash at polling
0
Off
1
On
09
---unused---
0
10
Sounder output
Activation
0
In case of main
alarm
1
At any alarm
11
---unused---
0
12
Calibration time
0-24
Corresponds to
time
13
Earth fault
detection
0
On
1
Off
14
Earth fault
sensitivity
0-9
0 = high
(<9,0V & >17,0V)
9 = low
(<4,5V & >22,0V)
15
Pre alarm
(for all detectors)
0
Off
1
On
16
Reset detector
test
0
Automatic
1
Manual
17
RS485 channels
1,2
Corresponds to
the numbers of
channels
18
Battery capacity
0
12 Ah
1
17 Ah
2
24 Ah
19
Buzzer at
information
0-1
0 = off
1 = on
20
Reset 1
st
alarm
0, 5-99 Min.
21
Calibration Fault
0-24
Time for message
display of
calibration faults.
22
call accept after
restart
0
off
1
on
30
I N I T I A L I S A T I O N
RSRS485 Devices : 001
------------------
Scanning RS485 devices
The FCP scans the serial interfaces for connected
LCD repeater panels and fire brigade repeater panels.
The number of recognized devices is displayed In the
last but one line (here: 1).
31
Scan detectors
Loop module : 01
Scan detectors
This menu relates to addressable detectors only.