NSC Sicherheitstechnik GmbH
10/47
2011 / 04 / 26
Eckendorfer Str. 125 c
Installation Manual Solution F2 20110509.doc
33609 Bielefeld
Version S031A01.01
02.1
Zones & detect.
Status
from zone : 5
programmed zone text
To zone :
Cancel On Off Detect.
Switching on/off: zones and single detectors
You can switch off single zones or several zones
simultaneously. This is done by using the “from …
to… “ function. Please type the zone number and
confirm by “OK”.
"Status“ means the current status of the zone (e.g.
normal, alarm, fault). To switch off the zone you have
to press "Off“ (F3) or for switching on the zone you
have to press "On“ (F2).
If only one zone shall be switched the line
"to zone“ can be missed and F2/F3 (on/off) can be
pressed immediately.
If single detectors shall be switched you have to type
“Detect.” (F4) after the zone has been confirmed (do
not use F2/F3 (on/off) in this case)
Jump to Menu
02.2
02.2
Zone 0005 Status
from detector : 1 normal
evt. individual detector text
to detector : 3 normal
evt. individual detector text
Cancel On Off
Switching on/off: Addressable detectors
The first line of the LC module shows the zone where
the detectors are located (here : 5).
It is possible just to switch off only one detector as
well as several detectors. Please type the detector
number and confirm by “OK”.
"Status“ means the current status of the detector (e.g.
normal condition, alarm condition, fault condition). If a
individual detector text has been configured, this text
will be displayed right below the detector line after
pressing “OK”.
For switching off you have to press "Off“ (F3) or for
switching on you have to press "On“ (F2).
If only one detector shall be switched the line "to
detector“ can be missed and F2/F3 (on/off) can be
pressed immediately.
02.3
Switch on/off
from output : 001 normal
to output :
↓
+1
↑
-1 Selection -> +10 <- -10
>001 Output 001 Main processor
002 Output 002 Main processor
003 Output 003 Main processor
Cancel On Off Enter
Switching on/off: OC-Outputs
Here the 8 OC-outputs on the main processor board
of the FCP "Solution F2” as well as the 9 OC-outputs
on the F2 io extension can be switched on/off.
Outputs 1 – 8 : OC- Outputs on main board
Outputs 9 – 17 : OC- Outputs on I/O extension
To switch on/off the outputs there are two possibilities
you can choose :
a) To type the output no. directly by the keypad and
confirming with "OK“. Please use the line “from
output” and “to output” for this.
b) Select the outputs by using the cursor keys
↓
and
↑
(means 1 line up or 1 line down) or the cursor
keys
and
(means 10 lines down or 10 lines
up) and confirm the output numbers with "Enter“
(F4) or “Ok”.
The actual "status“of the output (e.g. normal condition
or active) will be displayed behind the number.
After selecting the output / outputs you have to switch
them by pressing F3 („off“) or F2 („on“).