By a click on "Erase + Program" the selected flash functions will be executed.
During the updates a status display is shown in the lower part of the window. Here you can see the
progress of the flash programming procedure.
After the updates have finished you can leave the program by pressing the "Ende / Exit" button.
At the panel Solution F2 you can leave the flash update routine by pressing the "ESC" key. Then you
reach again the bootloader menu and you can start the firmware by pressing '1'. After a short time there
should bet the initialization display present followed by the display of recognized hardware modules.
Now you just have to switch off DIP switch 1 again (down position). This can be done while the system is
running.
After start of the new firmware you must do the following 2 steps.
1. Delete program and texts by "Prog" - "Installer" - "6 - settings" - "5 - Delete Program" and
"6 - Delte texts"
2. Download your programming file back to the panel.
Errors and possible reasons
In case of any problems during flash update you should try one of the following proposals. If there are
more than 1 proposal for any item you should always try no. 1 at first. I fit is not successful you should
continue with the next proposal.
Solution F2: Flash update routine "
Communication Fault"
The communication between the 2 microcontrollers didn't work correctly.
Remedy: 1. leave flash update routine by "ESC" and retry by pressing '2'
2. press hardware reset button on main board and start flash routine by pressing '2'
Solution F2: Firmware doesn't start
The flash area with the FCP firmware doesn't contain valid data.
Remedy: Please execute again the flash update. The main controller has to be erased and programmed
in any case, the loop controller usually can remain as it is.
Solution F2: after flash update the panel doesn't recognize any detectors
The flash update of the loop controller has missed, or the controller did not start correctly.
Remedy: 1. check that DIP switch 1 is off (down) and restart the panel by hardware reset button
2. execute again flash update fort he loop controller. The loop controller has to be erased and
programmed in any case, the main controller usually can remain as it is.
3. execute again the flash update for the main controller.