N-1000-III/IV
N-1000-III/IV
N-1000-III/IV
N-1000-III/IV
N-1000-III/IV
4–12
4–12
4–12
4–12
4–12
Section 4: P
Section 4: P
Section 4: P
Section 4: P
Section 4: Panel L
anel L
anel L
anel L
anel Layout
ayout
ayout
ayout
ayout
4-8: DIP Switch Settings
N-1000-III/IV DIP switch positions 1 and 2 control the panel baud rate for the 20
mA Loop. Set the panel baud rate to match that of the system programming
device. 1200 baud is recommended for computer and data terminal systems. For
485 communications use the 4800 baud setting.
N-1000-III/IV DIP switch positions 3 through 8 determine a control panel’s address.
(See Figure 4-8.) Each control panel in the communication loop must have a unique
address to allow unique referencing during system programming. When running the
panel’s self-test, set all DIP switches to the On position before restarting the panel.
(For details of the self-test, refer to Appendix C: Trouble Shooting.)
Baud rate and panel address DIP switch settings are as follow:
Baud Rate 1
2
Panel No. 3 4
5
6
7
8
1200
Off
Off
1
On
On
On
On
On
Off
2400
Off
On
2
On
On
On
On
Off
On
4800
On
On
3
On
On
On
On
Off
Off
9600
On
Off
4
On
On
On
Off
On
On
5
On
On
On
Off
On
Off
6
On
On
On
Off
Off
On
7
On
On
On
Off
Off
Off
8
On
On
Off
On
On
On
9
On
On
Off
On
On
Off
10
On
On
Off
On
Off
On
11
On
On
Off
On
Off
Off
12
On
On
Off
Off
On
On
13
On
On
Off
Off
On
Off
14
On
On
Off
Off
Off
On
15
On
On
Off
Off
Off
Off
16
On
Off
On
On
On
On
17
On
Off
On
On
On
Off
18
On
Off
On
On
Off
On
Figure 4-8.
DIP Switches.
Switch positions 1 and 2 control the panel baud rate for the 20
mA loop; switch positions 3 through 8 determine the control panel’s address. The positions above
are set for panel 1 and a baud rate of 2400.
Panel must be
earth grounded.
S-4 SUPPRESSION
REQUIRED ACROSS
EVERY ACTIVE RELAY
AND ELECTRICAL
DEVICE (CONNECT
WITHIN 18 INCHES).
Lock Solenoid
1
3
4
5
6
7
8
9
10
2
11
12
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
ON
}
Baud Rate
}
Panel Address