Chapter 37 Hardware procedures 243
Passport 7400 Hardware Installation, Maintenance, and Upgrade 5.2S1
•
You will need a multiport aggregate device with one of the following
PECs:
— NT0486AA (balanced, DC powered)
— NT0420AA (balanced, AC powered)
— NT0421AA (unbalanced, DC powered)
— NT0422AA (unbalanced, AC powered)
•
Before installing a multiport aggregate device, ensure that all cables,
including the power cables, are disconnected from the unit.
Procedure steps
1
Fasten a bracket to each side of the multiport aggregate device using two
of the screws and the flat washers provided. See the figure “Installing
brackets on a multiport aggregate device” (page 245).
2
If you are installing the first panel on the rack, connect the grounding wire
(supplied separately by Nortel Networks) to the top right securing screw.
See the figure “Grounding 19” termination panels” (page 206).
or
If you are installing the lowest panel on the rack, secure the bottom of the
grounding strip and a grounding wire to the rack with a screw.
3
Use a 5/16-inch socket wrench to secure the brackets to the cabinet or
rack with four of the screws provided.
Allow at least 90 cm (36 in.) clearance in front of the device for operator
access. Allow at least 10 cm (4 in.) clearance at the rear of the device for
cable connections.
WARNUNG
Verletzungsgefahr durch Stromschlag
Bevor Sie Kabel anschließen oder das Gerät einschalten,
vergewissern Sie sich, dass das Gerät vorschriftsmäßig
geerdet ist. Ist das Gerät nicht vorschriftsmäßig geerdet,
besteht Verletzungsgefahr für das Bedienpersonal und
das Risiko der Beschädigung des Geräts durch
Stromschlag. Nähere Informationen finden Sie unter
241-7401-200 Passport 7400 Hardware Description
Summary of Contents for Passport 7400
Page 1: ...Passport 7400 Hardware Installation Maintenance and Upgrade 241 7401 240 ...
Page 2: ......
Page 4: ......
Page 6: ...6 Publication history 241 7401 240 5 2S1 ...
Page 28: ...28 About this document 241 7401 240 5 2S1 ...
Page 32: ...32 Chapter 1 3 slot Passport switch installation 241 7401 240 5 2S1 ...
Page 42: ...42 Chapter 3 5 slot Passport switch installation 241 7401 240 5 2S1 ...
Page 60: ...60 Chapter 5 16 slot Passport switch installation 241 7401 240 5 2S1 ...
Page 66: ...66 Chapter 6 16 slot Passport switch shelf replacement 241 7401 240 5 2S1 ...
Page 74: ...74 Chapter 9 Alarm hardware replacement 241 7401 240 5 2S1 ...
Page 80: ...80 Chapter 11 BITS termination panel replacement 241 7401 240 5 2S1 ...
Page 84: ...84 Chapter 12 Cabinet installation 241 7401 240 5 2S1 ...
Page 88: ...88 Chapter 13 Cable replacement 241 7401 240 5 2S1 ...
Page 102: ...102 Chapter 18 Ethernet cable replacement 241 7401 240 5 2S1 ...
Page 106: ...106 Chapter 19 External timing addition 241 7401 240 5 2S1 ...
Page 110: ...110 Chapter 20 Failed FP cable replacement 241 7401 240 5 2S1 ...
Page 132: ...132 Chapter 25 Function processor decommissioning 241 7401 240 5 2S1 ...
Page 152: ...152 Chapter 32 Power cable replacement 241 7401 240 5 2S1 ...
Page 156: ...156 Chapter 33 Power supply addition 241 7401 240 5 2S1 ...
Page 160: ...160 Chapter 34 Power supply replacement 241 7401 240 5 2S1 ...
Page 412: ...412 Chapter 37 Hardware procedures 241 7401 240 5 2S1 ...
Page 436: ...436 Chapter 37 Hardware procedures 241 7401 240 5 2S1 ...
Page 437: ......