80
Commander S100 User Guide
7.3.4 Menu 4 - General
This menu contains parameters related to the general drive settings, communication setup parameters and miscellaneous functions such as defining
parameter values to store when an error occurs.
Figure 7-12 Menu 4 - General
Bit 15
Sequencer
Supply Loss Acon P4.08
No. of Auto -reset a empts
P4.12
Hold drive healthy on
Auto-reset a empts P4.13
Drive reset when Enable or
run applied P4.14
Control Word P4.18
Menu 4 - General
Serial Comms
Run &
Direcon
Indicators
P1.11
Sequencer Input and
Output Indicators
1
0
Menu 6 I/O
Configuraon
Node Address P4.03
Mode P4.04
Baud Rate P4.05
Transmit delay P4.06
Run & Direcon
Indicators P1.12
Bit
Funcon
0
Run Forward
1
Run Reverse
2
Run
3
Reverse
4
Jog Forward
5
Jog Reverse
6
Run Permit (Not Stop)
Sequencer Input and
Output Indicators P1.11
Bit
Funcon
0
Hardware Enable
1
Soware Enable
2
Forward Limit switch
3
Reverse Limit switch
4
Reference On
5
Reverse Reference
6
Jog Reference
7
UnderVoltage
Error System
Parameter Save 1 selector P4.09
Parameter Save 2 selector P4.10
Parameter Save 3 selector P4.11
Motor Phase Loss detecon P4.15
User Error P4.16
Drive Enable P4.17
Miscellaneous
Load Defaults P4.01
Security PIN P4.02
Save Parameters P4.19
Near Field Communicaon P4.20
Alarm Indicators P1.09
Bit
Funcon
0
Motor Overload
1
Drive Overload
2
Autotune acve
3
Limit switch acve
4
Input Phase loss or imbalance
5
4-20mA input loss
6
Current Limit acve
7
Digital output overload
Drive Status Indicators P1.10
Bit
Funcon
0
Supply Loss
1
Limit switch acve
2
Thermal Limit acve
3
Current Limit acve
4
Drive Acve
5
Drive Healthy
6
At Speed
7
Zero Speed
Drive
State
Saved
Parameter 1
Saved
Parameter 2
Saved
Parameter 3
Error
Error
History 1
Error
History 2
Error
History 3
Keypad Run/Stop
select P4.07
Up key
Down key
Reset key
P1.12
P1.26
P1.27
P1.28
P1.29
P1.30
P1.31
P1.32
P1.09
P1.10
P1.05
P1.11
Final Enable
P4.01
Restore Factory Defaults
Range:
0 to 2
Default:
0 (None)
Restores the default parameter settings of the drive and will clear any user configured parameter settings.
If this parameter is set to a value other than 0, then the drive will load the appropriate defaults and save parameters. This parameter will be reset
to 0 after the action is completed. If editing on the keypad the action will be performed when the edit is finished by pressing the settings button.
Restoring factory defaults cannot be undone.
If there is an attempt to restore defaults while the drive is running, the defaults will not be restored until the drive stops.
P4.02
Security PIN
Range:
0 to 9999
Default:
0
Defines the 4 digit security pin of the drive. This parameter can be set to a value other than 0 to prevent unauthorized write access to the drive.
When a value greater than 0 has been set, it will not be displayed on the keypad or Marshal app to maintain security. If a value has been set, the
security pin must be entered before any parameter can be adjusted via the keypad or prior to writing parameters to the drive via Marshal.
P4.03
Serial Node Address
Range:
1 to 247
Default:
1
Defines the serial address of the drive.
P4.04
Serial Mode
Range:
0 to 3
Default:
0 (8.2NP)
Defines the serial mode of the drive.
The drive always uses MODBUS RTU and is always a slave. All parameters can be accessed as 16-bit registers.
Value
Text
Description
0
None
No action
1
50 Hz
Restore Factory Defaults for 50 Hz region
2
60 Hz
Restore Factory Defaults for 60 Hz region
NOTE
Value
Serial Mode
Description
0
8.2NP
8 data bits, 2 stop bits, no parity bit
1
8.1NP
8 data bits, 1 stop bit, no parity bit
2
8.1EP
8 data bits, 1 stop bit, even parity bit
3
8.1OP
8 data bits, 1 stop bit, odd parity bit