This chapter covers additional technical data relating to the drive. This includes:
•
Drive deratings for 4 kHz and 12 kHz switching frequency for standard and increased ambient temperatures
•
Drive losses (Power dissipation)
•
Drive storage
•
Emission compliance for switching frequency and motor cable length cross reference
•
Maximum cable lengths for 12 kHz switching frequency
•
Miscellaneous drive data
•
IP rating description
•
Vibration test specification
Table 10-1 Environment specifications
1
2
See section 10.1.2
10.1 Drive derating
The drive output current must be derated when the drive is used in a suboptimal environment such as a higher altitude, increased ambient
temperature, reduced drive clearance, or if an increased switching frequency is used. The maximum continuous output current deratings in the
following tables should be used.
If a drive is to be mounted in a sealed enclosure with no air flow (<2 m/s) over the drive, select an operating temperature 5 °C above the measured
maximum internal temperature.
10.1.1 Temperature
Table 10-2 Maximum permissible continuous output current
Specification
Detail
Storage temperature
-40 °C to 60 °C (-40 °F to 140 °F)
1
Operating temperature without derate
-10 °C to 40 °C (14 °F to 104 °F)
Operating temperature with derate
-10 °C to 60 °C (14
°F to 140 °F)
Altitude
≤
3000 m (1000 m to 3000 m derate 1 % over 100 m)
2
Humidity
95 % non-condensing at 40 °C / 104 °F - EN61800-2(3k3)
Pollution
Pollution degree 2 -
Dry, non-conducting pollution only
IP Rating
IP20
Vibration
Tested to IEC 60068-2-6
Corrosive Environments
Concentrations of corrosive gases must not exceed the levels given in: EN 60721-3-3 ISO9223 Class
C3
Drive Model Number
Nominal Power
Rating
Maximum continuous
output current @ 40
o
C
Maximum continuous
output current @ 50
o
C
Maximum continuous
output current @ 60 °C
kW
hp
4 kHz
12 kHz
4 kHz
12 kHz
4 kHz
12 kHz
A
A
A
A
A
A
100 V Drive (100 to 120 V ±10 %)
S100-01113
0.18
0.25
1.2
1
1
1
1.8
1.8
S100-01123
0.25
0.33
1.4
1.2
1.2
1.2
1
1
S100-01133
0.37
0.5
2.2
1.4
1.4
1.4
1.2
1.2
S100-03113
0.55
0.75
3.2
2.2
2.2
1.6
1.4
1.4
S100-03123
0.75
1
4.2
3.2
3.2
2.2
2.2
2.2
S100-03133
1.1
1.5
6
4.2
4.2
3.2
3.2
3.2
Summary of Contents for COMMANDER S100