Commander S100 User Guide
57
7.2.3 Menu 3 - Motor setup
7.2.4 Menu 4 - General
Parameter
Range
Default
P3.01
Motor Rated Current
0.00 to Drive Rated Current (A)
Rating Dependent
P3.02
Motor Rated Speed
0 to 18000 rpm
Region Dependent
P3.03
Motor Rated Voltage
0 to Maximum Drive Output Voltage
Rating Dependent
P3.04
Motor Rated Power Factor
0.00 to 1.00
Rating Dependent
P3.05
Motor Control Mode
Resistance Comp (0), Linear V to F (1), Square V to F (2)
Linear V to F (1)
P3.06
Motor Starting Boost
0.0 to 25.0 %
3.0 %
P3.07
Motor Starting Boost End Voltage
0.0 to 100.0 %
50.0 %
P3.08
Motor Starting Boost End Frequency
0.0 to 100.0 %
50.0 %
P3.09
Perform Auto-tune
Off (0) or On (1)
Off (0)
P3.10
Energy Optimizer
Off (0) or On (1)
Off (0)
P3.11
Catch An Already Spinning Motor
Disabled (0), Enabled (1), Forward Only (2), Reverse Only (3)
Disabled (0)
P3.12
PWM Switching Frequency
4 kHz (0) or 12 kHz (1)
4 kHz (0)
P3.13
DC Braking Current Level
0.0 to 150.0 %
100.0 %
P3.14
DC Braking Time
0.0 to 100.0 s
1.0 s
P3.15
Motor Rated Frequency
0.0 to 300.0 Hz
Region Dependent
P3.16
Number Of Motor Poles
0 to 8
0 (Automatic)
P3.17
Torque Current Limit
0.0 to Torque Current Maximum Limit %
Rating Dependent
P3.18
Stator Resistance
0.00 to 199.99
Ω
2.00
Ω
P3.19
Motor Stability Optimizer
Off (0) or On (1)
Off (0)
P3.20
Reverse Motor Direction
Off (0) or On (1)
Off (0)
P3.21
Thermal Protection Action
Disabled (0), Error with Save (1), Error (2), Limit with Save (3), Limit (4)
Limit with Save (3)
P3.22
Low Frequency Thermal Protection
Off (0) or On (1)
On (1)
P3.23
Current Controller Gain
0 to 250
40
Parameter
Range
Default
P4.01
Restore Factory Defaults
None (0), 50 Hz (1), 60 Hz (2)
None (0)
P4.02
Security PIN
0 to 9999
0
P4.03
Serial Node Address
1 to 247
1
P4.04
Serial Mode
8.2NP (0), 8.1NP (1), 8.1EP (2), 8.1OP (3)
8.2NP (0)
P4.05
Serial Baud Rate
Disabled (0), 600 (1), 1200 (2), 2400 (3), 4800 (4), 9600 (5), 19200 (6), 38400 (7),
57600 (8), 76800 (9), 115200 (10)
115200 (10)
P4.06
Minimum Serial Comms Transmit
Delay
0 to 250 ms
0 ms
P4.07
Keypad Run and Stop Function Select
None (0), Run and Stop (1), Jog (2)
None (0)
P4.08
Supply Loss Action
Disable (0), Ramp Stop (1), Ride Through (2)
Disable (0)
P4.09
Parameter 1 Save on Error Selector
None (0), Output Frequency (1), Output Voltage (2), Output Power (3),
Motor RPM (4), Drive State (5), Output Current (6), Torque Current (7),
Percentage Load (8), Alarm Indicators (9), Status Indicator (10),
Seq. Indicators (11), Run and Direction (12), Ramp Input (13), Ramp Output (14),
T2 Analog 1 % (15), T4 Analog 2 % (16), T15 Frequency % (17),
Up/Down % (18), PID Percentage (19), PID Indicators (20), PID Error (21),
Motor Thermal % (22), Drive Thermal % (23), DC Bus Voltage (24),
IO Indicators (25)
Ramp Output (14)
P4.10
Parameter 2 Save on Error Selector
Output Current (6)
P4.11
Parameter 3 Save on Error Selector
DC Bus Voltage (24)
P4.12
Number of Auto Reset Attempts
None (0), One (1), Two (2), Three (3), Four (4), Five (5), Unlimited (6)
None (0)
P4.13
Hold Drive Healthy on Auto Reset
Attempts
Off (0) or On (1)
Off (0)
P4.14
Drive Reset When Enable or Run
Applied
Off (0) or On (1)
On (1)
P4.15
Motor Phase Loss Detection
Off (0) or On (1)
Off (0)
P4.16
User Error
0 to 255
0
P4.17
Drive Enable
Off (0) or On (1)
On (1)
P4.18
Binary Control Word
0 to 65535 (Binary 16 bit)
0
P4.19
Save Parameters
Off (0) or On (1)
Off (0)
P4.20
Near Field Communication (NFC)
Disabled (0), Read Only (1), Read & Write (2)
Read & Write (2)