Table 4-8 Line reactor ratings for 200 V drives
Table 4-9 Line reactor rating for 400 V drives
If the drive is installed on a system that differs from the values shown, calculate the required inductance using the equation below.
To calculate the inductance required (at Y %), use the following equation:
Where:
L = Inductance (H)
V = Line to Line Voltage (V)
f = Supply Frequency (Hz)
I = Drive Rated Input Current (A)
4.5.4 Main A.C. supply contactor
The recommended A.C. supply contactor type is AC1.
Model Number
Power rating
Power rating
Supply phases
Continuous
supply current
Minimum line
reactor
inductance
Control
Techniques part
no.
kW
hp
A
mH
S100-01S13
0.18
0.25
1
3.30
1.96
4401-0224
S100-01213
0.18
0.25
3
2
1.96
4401-0224
S100-02S11
0.18
0.25
1
3.30
1.96
4401-0224
S100-01S23
0.25
0.33
1
3.80
1.96
4401-0224
S100-01223
0.25
0.33
3
2.30
1.96
4401-0224
S100-02S21
0.25
0.33
1
3.80
1.96
4401-0224
S100-01S33
0.37
0.5
1
4.70
1.12
4401-0225
S100-01233
0.37
0.5
3
2.80
1.96
4401-0224
S100-02S31
0.37
0.5
1
4.70
1.12
4401-0225
S100-01S43
0.55
0.75
1
8
0.79
4401-0143
S100-01243
0.55
0.75
3
4.70
1.12
4401-0225
S100-02S41
0.55
0.75
1
8
0.79
4401-0143
S100-01S53
0.75
1
1
9.50
0.79
4401-0143
S100-01253
0.75
1
3
5.70
1.12
4401-0225
S100-02S51
0.75
1
1
9.50
0.79
4401-0143
S100-01D63
1.1
1.5
1/3
15.30
0.48
4401-0144
S100-02S61
1.1
1.5
1
15.30
0.48
4401-0144
S100-01D73
1.5
2
1/3
18.40
0.48
4401-0144
S100-02S71
1.5
2
1
18.40
0.48
4401-0144
S100-03D13
2.2
3
1/3
26.10
0.32
4401-0145
Model Number
Power rating
Power rating
Supply phases
Continuous
supply current
Minimum line
reactor
inductance
Control
Techniques part
no.
kW
hp
A
mH
S100-02413
0.37
0.5
3
1.90
2.94
4401-0148
S100-02423
0.55
0.75
3
2.50
2.94
4401-0148
S100-02433
0.75
1
3
3
2.94
4401-0148
S100-02443
1.1
1.5
3
4.50
2.94
4401-0148
S100-02453
1.5
2
3
5.60
2.94
4401-0148
S100-02463
2.2
3
3
8.20
1.62
4401-0149
S100-03413
3
3
3
13.20
1.05
4401-0151
S100-03423
4
5
3
16
0.79
4401-0152
L
=
Y
x
V
x
1
100
√
3
2
π
fI