110
Commander S100 User Guide
10.2 Power dissipation
Table 10-3 Drive losses
10.3 Drive storage
-40 °C (-40 °F) to +60 °C (140 °F) for long term storage.
Storage time is 2 years.
Low voltage capacitors cannot be reformed due to their location in the circuit and thus may require replacing if the drive is stored for a period of 2
years or greater without power being applied. It is therefore recommended that drive are powered up for a minimum of 1 hour after every 2 years of
storage. This process allows the drive to be stored for a further 2 years.
Drive Model
Number
Power Rating
Supply Phases
Standby Drive Losses
Drive Losses at Rated
Power
Efficiency
kW
hp
W
W
%
100 V Drives
S100-01113
0.18
0.25
1
3.1
9.9
96.1
S100-01123
0.25
0.33
1
3.1
12.3
96.4
S100-01133
0.37
0.5
1
4
17.8
96.2
S100-03113
0.55
0.75
1
4
24.7
96.4
S100-03123
0.75
1
1
3.4
40.8
95.8
S100-03133
1.1
1.5
1
3.2
54.5
95.5
200 V Drives
S100-01S13
0.18
0.25
1
4.2
12.3
96.4
S100-01213
0.18
0.25
2
4.2
11.2
96.4
S100-02S11
0.18
0.25
1
3.7
10.7
96.2
S100-01S23
0.25
0.33
1
4.2
13.8
96.7
S100-01223
0.25
0.33
2
4.2
12
96.7
S100-02S21
0.25
0.33
1
3.7
12.9
96.6
S100-01S33
0.37
0.5
1
4.2
18.4
96.5
S100-01233
0.37
0.5
2
4.2
16.3
97
S100-02S31
0.37
0.5
1
3.7
21.4
95.8
S100-01S43
0.55
0.75
1
4.1
26.6
96.8
S100-01243
0.55
0.75
2
4.2
24.7
97.2
S100-02S41
0.55
0.75
1
4.5
26.5
96.7
S100-01S53
0.75
1
1
4.1
24.7
96.9
S100-01253
0.75
1
2
4.3
26.5
97
S100-02S51
0.75
1
1
4.7
33.9
96.8
S100-01D63
1.1
1.5
1
5.2
42.9
97.0
3
5.7
37.3
97.4
S100-02S61
1.1
1.5
1
3.4
43.1
97.1
S100-01D73
1.5
2
1
4.3
57.5
96.7
3
4.0
48.5
97.3
S100-02S71
1.5
2
1
4.4
62.7
96.8
S100-03D13
2.2
3
3
3.0
93.9
96.4
1
4.0
76.8
97
400 V Drives
S100-02413
0.37
0.5
3
6.9
18.2
96.9
S100-02423
0.55
0.75
3
10.5
24.5
97
S100-02433
0.75
1
3
6.8
26.8
97.3
S100-02443
1.1
1.5
3
6.8
34.3
97.6
S100-02453
1.5
2
3
6.5
45.4
97.6
S100-02463
2.2
3
3
6.5
89.3
96.9
S100-03413
3
3
3
6.6
84.6
97.6
S100-03423
4
5
3
6.4
118.6
97.6
Summary of Contents for COMMANDER S100