3.89
EDH0162En1040 – 06/99
MM4005
OH — Set home search high velocity
Usage
IMM
PGM
MIP
Syntax
xxOHnn
Parameters
Description
xx
[int]
— Axis number.
nn
[float]
— Home search velocity.
Range
xx
—
1
to
4.
nn
—
0.000001
to
Maximum motion speed defined in
SETUP
.
Units
xx
— None.
nn
— Units/sec.
Defaults
xx
Missing: Error B.
Out of range: Error B.
Floating point: Error A.
nn
Missing: Error C.
Out of range: Error C.
Description
This command sets the high velocity of the HOME search algorithm of the
selected axis.
For a detailed description of the home search routine see the Home Search
paragraph in the Motion Control Tutorial section.
Returns
None.
Errors
A
—
Unknown message code.
B
—
Incorrect axis number.
C
—
Parameter out of limits.
Rel. Commands
DO
—
Read home search velocity.
OR
—
Search for home.
Example 3OH10
|
Set home search high velocity of axis #2 to 10 units/sec.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com