P R O G R A M M I N G
NESS D16 (V4.6) CONTROL PANEL - INSTALLER MANUAL
MONITOR MODE OUTPUT MAPPING
This option selects which outputs are triggered by alarms in Monitor Mode.
PROGRAMMING SEQUENCE:
P63E 1E-4E
toggles the options ON and OFF
P63E 1E: Monitor Mode to Reset output
P63E 2E: Monitor Mode to Strobe output
P63E 3E: Monitor Mode to Keypad Sonalert output
P63E 4E: Monitor Mode to Siren output
P63E 1E-4E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
1E-4E OFF: No Monitor Mode outputs
NOTES:
• RELATED OPTIONS:
P64E 1E
2second Monitor alarm
1E 2E 3E 4E 5E 6E 7E 8E
ON = Factory default setting.
Monitor to R
eset output
Monitor to Strobe output
Monitor to Sonaler
t output
Monitor to Siren output
Day Mode to R
eset output
Day Mode to Strobe output
Day Mode to Sonaler
t output
Day Mode to Siren outpu
t
OPTION No
DESCRIPTION
P63E
Monitor & Day mode output mapping
ON ON
DAY MODE OUTPUT MAPPING
This option selects which outputs are triggered by alarms in Day Mode.
PROGRAMMING SEQUENCE:
P63E 5E-8E
toggles the options ON and OFF
P63E 5E: Day Mode to Reset output
P63E 6E: Day Mode to Strobe output, (If Brief Day Alarm is enabled, (P64E 2E), then this
option sends day alarms to the AUX2 output).
P63E 7E: Day Mode to Keypad Sonalert output
P63E 8E: Day Mode to Siren output
P63E 5E-8E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
5E, 6E ON
7E, 8E OFF
NOTES:
• RELATED OPTIONS:
P64E 2E
2second Day alarm
For ZONE TO OUTPUT MAPPING (Armed & 24hr states)
- see Options P54E - P59E, page 22
MONITOR Mode and DAY Mode Output Mapping is an extra feature released
with the D16.
Note that MONITOR and DAY zones do not automatically assume the outputs
assigned by Options P54E-P59E. Those options only apply to zones when the
panel is in the ARMED state.
Options P63E 1E-8E allow different outputs to be triggered when the panel is in
MONITOR and DAY modes.