Chapter 2: Site Preparation
2-9
RealScan Checkstand Wiring
Feeder wiring and insulated ground from
main service panel to distribution panel
to be run in metal conduit.
The electrical wiring must meet all
electrical codes, laws, and regulations.
Note:
Circuit Breakers
NCR circuits should be run in
separate metal Conduits.
Isolated/Insulated
Ground Bus
Neutral and
Ground Bus
Neutral
Bus
Input
Voltage
Input Voltage
L1
Circuit Breakers
U.S., Canada, &
Japan
European
International
100Vac to 120Vac
220Vac
220Vac to 240Vac
100Vac to 120Vac
220Vac
220Vac to 240Vac
Standard single-pole; value
determined by type of device
branch and by electrical code.
European double-pole.
Circuit B: Terminal and Scanner/Scale
Receptacle should be easily
accessible and near the
Scanner/Scale
Installation Type
NCR circuits must be dedicated to
NCR equipment or other logically
connected electronic equipment
(modems, DAA, bridges, etc.)
Note:
L2
Distribution Panel
Main Service
Panel
Conduit
Checkstand
Frame
Circuit A: Checkstand
Belt
Motor
Belt Control
Lighting
Misc. Equip.
N
G
L1
25729
Isolated Ground Receptacles
Summary of Contents for 74 OFX (7874)
Page 1: ...NCR RealScan 74 OFX 7874 Release 1 1 User Guide 25315 B005 0000 1822 Issue C...
Page 16: ......
Page 42: ......
Page 240: ......
Page 246: ......
Page 248: ...A 2 Appendix A NCR Scanner Programming Tags Reset 11818 Default R0046 Programming Mode R0042...
Page 249: ...Appendix A NCR Scanner Programming Tags A 3 End R0043 Save and Reset R0044 Abort R0045...
Page 253: ...Appendix A NCR Scanner Programming Tags A 7 Hex 2 R0050 Hex 3 R0051 Hex 4 R0052...
Page 254: ...A 8 Appendix A NCR Scanner Programming Tags Hex 5 R0053 Hex 6 R0054 Hex 7 R0055...
Page 255: ...Appendix A NCR Scanner Programming Tags A 9 Hex 8 R0056 Hex 9 R0057 Hex A R0058...
Page 256: ...A 10 Appendix A NCR Scanner Programming Tags Hex B R0059 Hex C R0060 Hex D R0061...
Page 258: ......
Page 264: ......
Page 266: ......