NAPCO iSecure Installation & Programming Instructions Download Page 33

Napco iSecure Security System

                         

All technical manuals are available in PDF format at 

tech.napcosecurity.com

 

33

 

12.  Install Takeover Module

 

DESCRIPTION

 

The 

ISEC

-

WL

-

MODULE

 is a "takeover module", used to convert 

an  existing  wired  security  system  to  wireless.    The 

ISEC

-

WL

-

MODULE

 will convert a total of 8 wired zones and convert them 

into 8 supervised wireless 900MHz zones.  For example, if you 

have existing wired security system sensors such as motion de-

tectors,  glass  break  sensors  and  door/window  transmitters,  you 

can use the existing wiring for each of these devices and convert 

them  into  iSecure  system  wireless  zones.    Up  to  4 

ISEC

-

WL

-

MODULE

s  are  allowed  with  each  Go

-

Anywhere  Smart  Hub.  

Note:

  For existing 2

-

wire smoke detectors, the 

ISEC

-

2WF

-

MOD

 

2

-

Wire  Fire  Sensor  Module

  may  be  used  if  the  detectors  are 

compatible (see page 36 for the list of compatible detectors and 

additional information).  

Note:

  Pressing the keypad 

RESET 

but-

ton  sends  an  updated  zone  status  and  module  status  from  the 

ISEC

-

WL

-

MODULE

 to the Hub.  In addition, 

LED1

 turns on for 

10 seconds.  Remove power from smoke detectors for 10 sec-

onds to reset.  See page 54 for full programming information.  

 

 

WIRING

 

In general, the first step for wiring the 

ISEC

-

WL

-

MODULE

 is to 

connect all of the Zone data wires to a mounted and 

unpowered

 

ISEC

-

WL

-

MODULE

.  Only after all zone and other wiring is con-

nected  should  you  then  power  the 

ISEC

-

WL

-

MODULE

  using 

either the existing wired 12VDC power connections from the ex-

isting security control panel or by an auxiliary power supply.  

 

Connect  the  high  side  (positive)  of  each  wired  zone  to  its  own 

screw  terminal,  labeled 

Z1

Z2

, etc. on  the 

ISEC

-

WL

-

MODULE

 

terminal strip.  Note that several sensors can be wired to a single 

zone  provided  they  are  wired  in  series.    Connect  the  low  side 

(negative)  of  each  wired  zone  to  any  of  the  ground  terminals 

(labeled 

GND 

next to each zone terminal).  

 

After all zone wires are connected, connect the battery 12V posi-

tive  lead  to  the 

BATT+

  terminal  on  the 

ISEC

-

WL

-

MODULE

.  

Connect the battery ground lead to any 

GND 

terminal.  After the 

battery  is  connected,  then  connect  the  12V  positive  regulated 

control  panel  (or  auxiliary  supply)  power  to  the 

+12V

  terminal 

followed by the negative ground connection to any 

GND 

terminal.

 

Wire  all  zone  and  power  connections  using  18

-

22AWG  wire.  

Install  end

-

of

-

line  resistors  on  all  zones,  even  if  one  or  more 

zones are not used.  

 

Note: 

 If battery voltage falls below the minimum level, a battery 

trouble is triggered; if the voltage climbs above the minimum lev-

el, the trouble will restore 30 seconds after pressing the keypad 

RESET 

button.  If 

RESET 

is not pressed, the battery trouble will 

self

-

restore  in  4  hours  if  the  battery  voltage  always  remains 

above the minimum level during this time.  

 

 

TERMINAL DESCRIPTIONS

 

Configure all inputs and outputs using the Management Center 

(the  Napco  "NOC"  located  at 

www.iSecureByNapco.com

).    Lo-

cated at the bottom of the PC board, the 20 terminals are:

 

 

EARTH

 .... 

This optional earth ground terminal provides protection 

from high

-

voltage transients (for example, nearby light-

ning discharges induce high

-

voltage transients into the 

field  wiring  of  electronic  equipment).    Therefore,  con-

nect this terminal to a metal cold

-

water pipe or a long 

steel  (or  copper)  ground  rod  driven  deeply  into  the 

earth.    Do  not  use  a  gas  pipe,  plastic  pipe  or  AC 

ground  connections.    Use  at  least  16

-

gauge  wire.  

Make the run as short and direct as possible, without 

any sharp bends in the wire.  

 

 

16VAC

 

SUPV

 ...... 

(Left terminal; some PC boards may indicate "

AC

" or 

"

ACL

") Non

-

polarized  16VAC terminal used  for  moni-

toring AC (

for  supervision  only,  not  power

).  Con-

nect  to  AC  power  source  terminal  (power  supply  or 

Hub power).

 

 

 

(Right terminal; some PC boards may indicate "

AC

" or 

"

ACN

") Non

-

polarized 16VAC terminal used for moni-

toring  AC.    Connect  to  AC  power  source  terminal 

(power supply or Hub power).

 

 

+12V

 ........ 

+12 volts DC to power the 

ISEC

-

WL

-

MODULE

.  Con-

nect this terminal to the Hub 

PGM (+) 

terminal or to the 

+12VDC terminal of the dedicated power supply  

 

 

GND

 ...... 

Common ground terminal for all sensors (all 

GND 

ter-

minals are electrically equivalent).  Therefore, connect 

the low side (negative) lead of each wired zone to the 

GND 

terminal next to each zone terminal (labeled 

Z1

Z2

, etc.).  

 

In addition, for the purpose of powering the 

ISEC

-

WL

-

MODULE

, connect this terminal to the Hub 

(‒) 

Auxilia-

ry Power or to the 

(‒) 

12VDC of the dedicated power 

supply.  

 

 

Z1+ 

 

-

 Z8+

 ........ 

Connect  the  high  side  (positive)  lead  of  each  wired 

zone to its own screw terminal, labeled 

Z1

Z2

, etc., for 

each zone 1 through 8, respectively.  

 

 

F PWR

 ..... 

Fire  Reset  (output).    Pressing 

RESET 

on  a  system 

keypad causes  this output  to change state (on  to  off, 

off  to on)  for 10 seconds.   Typically used  to create  a 

power output for latching 4

-

wire smoke detectors and 

similar  devices  that  require  power  to  be  removed  for 

reset.  May also be used on door latches that normally 

require  power,  thus  power  is  removed  on  a  "Fire 

Alarm" event.

 

 

BATT+

 ..... 

Optional connection to the existing Hub b termi-

nal (or + terminal of the power supply) for power super-

vision.  Place shunt across 

JP3 

to enable supervision.   

 

 

PNL+

 ....... 

Ex12VDC power input used to power the 

FIRE 

terminal  (described  above).    Remove  jumper 

JP13 

when 

FIRE 

output  is  powered  by  an  external  power 

source  (for  example,  wired  to  the  DC+  output  of  an 

Some PC boards may 

indicate "

AC

" and "

AC

or "

ACL

" and "

ACN

EARTH 

+12V 

GND

 

Z1+  Z2+ 

GND

 

Z3+  Z4+ 

GND

 

Z5+  Z6+ 

GND

 

Z7+  Z8+ 

GND

 

PNL+ 

16VAC SUPV 

F PWR 

BATT+ 

continued

 

Summary of Contents for iSecure

Page 1: ...Napco iSecure Security System All technical manuals are available in PDF format at tech napcosecurity com 1 NAPCO 2021 WI2240ALF 6 21...

Page 2: ...It is subject to change without notice Companies names and data used in examples herein are fictitious unless otherwise noted Napco assumes no responsibility for incor rect information this manual ma...

Page 3: ...Install the ISEC ZWAVE 40 Install the ISEC EXTANT KIT optional 41 Go Anywhere Smart Hub Icons 43 PROGRAMMING Programming Keypads Touchscreens 44 Programming Motion Sensors 45 Programming Glass Break S...

Page 4: ...382LF Hub tamper in stallation instructions included All Kits support up to six 6 ISEC WL KEYPADs and or ISEC WL TOUCHs combined When the Go Anywhere Hub is connected to a network with a Wi Fi access...

Page 5: ...gin Refer to the OI404LF card and enter your Dealer User ID Password and Radio ID iSecure LTE ID Click Submit D Click General Settings and in the Master Security Code field enter the Master Code also...

Page 6: ...within 15 minutes of checkout With iSecure a new subscriber account will automatically be created A Dealer User ID and temporary Password will be emailed to you the dealer upon activation This tempora...

Page 7: ...r the first time In the confirmation popup click Yes download to send all changes to the Go Anywhere Smart Hub Network MAC Unique Media Ac cess Control identifier assigned to the integral network inte...

Page 8: ...to enable the IP path of the integral dual path radio communicator this selection is available depending on plan purchased Configuration Type Click the Configuration Type pull down to select the re po...

Page 9: ...e iSecure Cloud Web Portal Note Radio will reboot after the successful download of new IP configurations IMPORTANT Some police and or fire departments require alarm permits contact each department do...

Page 10: ...or 5AH battery not supplied observing polarity secure battery with Velcro strap 7 Remove the plastic protective film from the face of the Go Anywhere Hub STAND ALONE INSTALLATIONS If placing on a she...

Page 11: ...s speakers or a mechanical bells this terminal and BELL Any self contained external siren requiring a 12V supply can be connected When connecting a mechanical bell it must be supervised using a 2 2k O...

Page 12: ...o place 4 Drill the two keypad mounting holes four holes with the IBR TOUCH WL in the mounting surface When mounting to hollow drywall or similar surface we recommend using wall anchors or similar har...

Page 13: ...security system keypad tap Keypad Only jump to step 6 To include video camera and Z Wave functions tap Full Functionality 4 5 Add the IBR TOUCH WL Tablet Kit 3 Only The steps below are the only steps...

Page 14: ...dministrator account User ID and Password and tap Finish 10 Upon connection to the Internet based ac count for the iSecure system the resulting keypad shown in step 12 will be configured for the payme...

Page 15: ...ON The ISEC MOTION is an advanced PIR sensor designed for use with Napco s wireless receivers The unit is powered by two sup plied 3 volt lithium batteries estimated battery life 3 years If bat tery v...

Page 16: ...as a template to mark mounting holes on the wall The sensor must be in direct line of sight of all windows being protected Reliable detection cannot be expected around cor ners in other rooms etc For...

Page 17: ...ector is mounted on the same wall as the glass point the tester at the opposite wall If the LED on the detector comes on for about 4 seconds when the tester is triggered the glass is within detection...

Page 18: ...DESCRIPTION The ISEC DW XMITTER is a low profile window door transmitter designed for use in Napco iSecure wireless systems Used with the supplied magnet the transmitter functions as a window door se...

Page 19: ...location to mount the ISEC SMOKE Note Mounting the ISEC SMOKE on foil backed wallpaper is NOT recommended because the radio range will be reduced The ISEC SMOKE is a high quality photoelectric smoke...

Page 20: ...e correct zone on the Hub and that the correct report is sent to the central sta tion NOTE Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found s...

Page 21: ...utomatically exit this mode after 5 minutes Note If smoke is still present in the chamber after exiting Silence mode the detector will go into alarm again IMPORTANT Use proper polarity when installing...

Page 22: ...eratures Also do not locate alarm in front of air conditioners heating registers or other locations where normal air circulation will keep smoke from entering the detector Installing smoke detectors i...

Page 23: ...onitor and annunciate low battery Coding switches are not required or used in the ISEC HEAT Each transmitter is assigned a unique identification code number at the factory The transmitter is powered b...

Page 24: ...ystem Test system with unit mounted If the system is monitored notify the central station of the impending test The rate of rise feature may be tested by a quick applica tion of heat from any convenie...

Page 25: ...ta or Sanyo type 123A battery in its compart ment observing correct polarity Enroll the ISEC CARBON MON into the Hub before mounting During power up and status initialization both the green and red LE...

Page 26: ...ss and hold the re cessed TEST button for approximately 2 seconds The detector will temporarily go into alarm and the red LED will illuminate b Within a few seconds the green LED will start to blink r...

Page 27: ...e equipment manufacturer s doc umentation or contact the manufacturer s directly for more information about how the equipment can leak carbon monoxide into the premises Ensure all motor vehicles are n...

Page 28: ...installation instructions in their entirety be fore installing the ISEC CARBON MON detector Leave these instructions with the owner user of the detector The ISEC CARBON MON is intended for use in ind...

Page 29: ...detector indicates an end of life condi tion whichever comes first CO detectors are not a substi tute for designated life safety devices Napco does not war rant or imply in any way that a CO detector...

Page 30: ...uit board no more than 45 degrees see Figures 1 and 2 to allow removal of batteries from the bottom circuit board 3 Slide the bottom battery out and away from the circuit board Figure 3 Top View of Bo...

Page 31: ...to which transmitter is applicable The 6 digit RF ID code with checksum digit printed on the transmitter enter all numbers and or letters including lead ing zeros if any Aux 1 option and Aux 2 option...

Page 32: ...t 3 Use the supplied double backed tape to secure the Tamper Magnet to the wall do NOT use any screws near electrical wiring that runs inside walls 4 At the wall outlet remove the wall cover plate scr...

Page 33: ...on If RESET is not pressed the battery trouble will self restore in 4 hours if the battery voltage always remains above the minimum level during this time TERMINAL DESCRIPTIONS Configure all inputs an...

Page 34: ...through JP12 for ZONE 8 Each zone 1 8 is assigned to terminals Z1 through Z8 respectively Notice each jumper block labeled JP5 through JP12 contains vertical 4 pins FIRE top two pins Selected zone rep...

Page 35: ...UMPER ZONE 1 FIRE CO BURG SET JUMPER ZONE 7 FIRE CO BURG SET JUMPER ZONE 8 FIRE CO BURG P2 1 2 3 4 5 6 BAT BAT DC DC 12 18VAC TRANSFORMER Control panel power or auxiliary power supply FIRE CO BURG ZON...

Page 36: ...zone 7 FIRE PR Connects to the positive terminal of the two wire smoke sensor Z8 Connects to the negative terminal of the two wire smoke sensor zone 8 Connect the 2 wire smoke detectors to the Go Anyw...

Page 37: ...MOD INSTALLATION If the Go Anywhere Smart Hub enclosure is not already open open the enclosure as directed on page 10 step 3 Remove all A C and battery power and install the ISEC 2WF MOD into the iSe...

Page 38: ...t secure the Go Anywhere Hub motherboard PCB to the front housing See the arrows in Fig 2 for screw locations 8 With the ISEC WIFI PC board in hand connect the small Antenna Board plug to the ISEC WIF...

Page 39: ...orks pull down find and select the SSID name of the customer s network Upon selection the Security Type and Selected Network fields will automatically populate Type the Password of the customer s Wi F...

Page 40: ...our body or clothing Use a grounded wrist strap or touch an unpainted grounded metal object If replacing an older version of the ISEC ZWAVE first down load the latest version of the Z Wave firmware at...

Page 41: ...e front LED Faceplate to the front housing 4 Remove the LED Faceplate From the front of the housing pull out the LED Faceplate to remove 5 On the inside of the LED Faceplate remove the screw that secu...

Page 42: ...lose the two parts of the Hub housing routing the cable out the rear access door see Fig 9 Be sure not to crimp the wire between the PCB and the housing Closing the two parts of the Hub housing will r...

Page 43: ...Receiver trouble due to excessive radio noise in area Try relocating the Smart Hub Otherwise call for service Rapid Flicker Transmissions in progress Flashing 900MHZ peripheral download Status Off No...

Page 44: ...he ISEC WL TOUCH press and hold the appropriate FIRE AUX or PANIC button respectively see the User s Guide for details By default Emergency Buttons are ena bled for all keypads to disallow their use s...

Page 45: ...R FUNCTION Select Instant or Interior When armed STAY usually when sleeping and you want the motion to ignore movement within the home select Interior If you want the sensor to immediately trigger an...

Page 46: ...it sensor ID for the device 4 DESCRIPTION Type the sensor descrip tion you wish to appear on the keypad display AREA Default 1 See the key pad Operating Guide for the definition of Area SENSOR FUNCTIO...

Page 47: ...or For example use for an interior door that will be in use when armed STAY but protected when armed AWAY Instant Allows for an immediate alarm when activated providing instant protection while you or...

Page 48: ...N Type the sensor descrip tion you wish to appear on the keypad display SENSOR TYPE Select Smoke Sensor SENSOR FUNCTION Smoke is au tomatically se lected when Smoke Sen sor is selected as the SENSOR T...

Page 49: ...on the keypad display SENSOR TYPE Select Heat Sensor SENSOR FUNCTION Heat is auto matically select ed when Heat Sensor is se lected as the SENSOR TYPE SENSOR ID Type in the 7 digit sen sor ID for the...

Page 50: ...or DESCRIPTION Type the sensor descrip tion you wish to appear on the keypad display SENSOR TYPE Select Carbon Monoxide SENSOR FUNCTION CO Alarm is automatically selected when Carbon Mon oxide is sele...

Page 51: ...the following Instant Allows for an immediate alarm when the panic button is pressed providing instant protection 24Hr Zone Audible Provides protection at all times whether or not the system is armed...

Page 52: ...e Select to disable the designated key Key 3 and or Key 4 Panic Pressing the designated key causes the siren to sound and sends a panic report to the central station Instant Pressing the designated ke...

Page 53: ...in any Area ISEC WL SIREN Wireless Siren TYPE Sirens can be powered by an AC power supply plugged into a 120VAC unswitched wall outlet or with batteries Select the power type used by your siren NAME...

Page 54: ...ired zone to the RF ID of the supervised 900MHz wireless zone up to 8 zones for each ISEC WL MODULE In the TAKEOVER screen shown below for the Takeover Module added previously program each column as d...

Page 55: ...umn 3 To add a new Code click in a blank USER CODES field and enter the new User Code up to 6 digits To erase or change an existing Code simply clear or re enter the User Code 4 Add a check to either...

Page 56: ...ng to establish a connection if this code is forgotten the Master Security Code of the particular Go Anywhere Hub can be used in its place Dealer Keypad Programming Code This code is left blank in the...

Page 57: ...at you wish to be used in text and email notification messages to help you identify the iSecure system installation Video Security Z Wave Remote Access Check to enable access to each service from the...

Page 58: ...can also be configured to allow Wi Fi con nections to only specific MAC Addresses Displays the MAC Address of the Go Anywhere Hub in an easy to copy field should it be needed Users Displays the USER I...

Page 59: ...sor within the Go Anywhere Hub that controls the radio communications between the Hub and the wireless de vice s Other iSecure Cloud Web Portal Screens cont d RadioHardware Version refers to the versi...

Page 60: ...relocate the Go Anywhere Smart Hub or the device so they are in closer proximity E 05 NN Transmitter Low Battery When an RF device has a weak battery an error E 05 appears The NN is a two digit number...

Page 61: ...top as shown in the image Note Never use the jumper position N A Use hearing protection siren is rated at 85dBA Do not apply AC power when rear cover is open 1 Remove AC and batteries 2 Remove jumper...

Page 62: ...h the same type as specified above Use of other types may present a risk of fire or explosion Nev er recharge or disassemble a battery or dispose of in fire E06 NN Receiver Response Failure Call insta...

Page 63: ...TER When the test is initiated data is transferred back and forth be tween the keypad and Hub When finished the signal levels of both the keypad and Hub are displayed and a beep is heard in the sequen...

Page 64: ...Secure system might be interfering with the system to be installed the ISEC WL KEYPAD can be used as a scanner to scan for the presence of other nearby iSecure radio signals and determine if the nearb...

Page 65: ...unication link between the Hub and the ISEC WL TOUCH keypad was interrupted If Out of System this field will count down AutoEnroll This feature is a quick and easy way to enroll wireless devices into...

Page 66: ...w E02 00 will appear in the display indicating a low battery condition Allow 24 hours for the battery to recharge DISPLAY SYS TRBL Displays all system error codes troubles LOW BAT TERY AC POWER LOSS e...

Page 67: ...pertinent information where necessary depending upon the event TO ARM IN 1 4 HRS Use this function to a delay programmed auto arming up to 4 hours 15 minutes or b initiate auto arming in 4 hours 15 mi...

Page 68: ...scribed below tap Config ure otherwise tap Continue to App to return to the Home Screen or Test Again to repeat the test See page 13 for step by step instructions to help guide you through the Wiz ard...

Page 69: ...1 3 5 7 10 15 and 20 minutes BSSID used to LOCKDOWN IBRIDGE Tap to enter a new broadcast SSID named BSSID in this menu to be stored in the touchscreen s memory to be used by default when the touchscre...

Page 70: ...then connect power to the camera Do you wish to proceed with Wire less Camera Configuration 1 The camera must be powered and wirelessly con nected to the network before proceeding 2 Tap Yes to procee...

Page 71: ...wish to disallow customer changes to the home automation Z Wave system unchecking disabling this setting disables the User Settings menu feature named Automation Management z wave Converse ly check t...

Page 72: ...hours with network connection 32 hours ISEC KIT2 Battery Standby Hours 12V 4AH battery No network connection 25 hours with network connection 24 hours 12V 5AH battery No network connection 32 hours w...

Page 73: ...RT HUB In cludes up to 80 wireless zones in 1 or 2 discrete Areas with keypad bus and other optional con nections Kits with the suffix V use the Verizon network A use the AT T network IBR TOUCH WL Sma...

Page 74: ...s re ceivers The ISEC MOTION is powered by two supplied 3 volt lithium batteries estimated battery life 3 years When battery voltage drops below normal a low battery report will be sent to the re ceiv...

Page 75: ...Wireless Siren Mounting Template Slide Screw Use with battery powered units only Magnet 1 5 8 Align this centerline with Wall Socket 7 16 Magnet Screws 2 Use with battery powered units only Center Lin...

Page 76: ...76 All technical manuals are available in PDF format at tech napcosecurity com Napco iSecure Security System Notes...

Page 77: ...rews 2 Use with battery powered units only Center Line of Wall Socket 5 1 4 Screw Hole Tab Align this centerline with Wall Socket This template shows the unit plugged into the bottom receptacle but ei...

Page 78: ...78 All technical manuals are available in PDF format at tech napcosecurity com Napco iSecure Security System ISEC WL MODULE Takeover Module Wiring Diagram...

Page 79: ...Napco iSecure Security System All technical manuals are available in PDF format at tech napcosecurity com 79 iSecure Hub Wiring Diagram LA3550A3...

Page 80: ...he product Seller s warranty as hereinabove set forth shall not be enlarged diminished or affected by and no obligation or liability shall arise or grow out of Seller s rendering of technical advice o...

Reviews: