52
Specifications
Loop Load
Min
Nom
Max
Units
Quiescent Current
300
mA
Sounder Circuits
External PSU Input Voltage
20
24
30
V
External PSU Current Rating
1
A
Sounder Load (Each Channel)
300
mA
End Of Line Resistance
12±5%
k
External PSU Monitor Input
End Of Line Resistance
12±5%
k
Fault Input Trigger Resistance
100
Environmental
Operating Temperature
-10
+60
°C
Humidity (Non Condensing)
95
%rh
Standards
UL864 9th Edition
Compatibility
Suitable for use with MA-1000 Analog Addressable Fire Panels
Physical
Dimensions 147 x 88 x 57 (mm)
Weight 0.25kg
Ingress Protection IP40
Short Circuit Isolator
This addressable device contains an integral short circuit isolator, which operates between the
– IN
terminal and the
– OUT terminal. The isolator operates in conjunction with Analog Addressable Control Panels when a
low parallel resistance fault of typically 200
Ω is present between the +VE and –VE of the loop wiring.
Short Circuit Isolation Data
(Integral with each device)
Total Loop Resistance for correct
operation of short circuit isolator
50Ω (max)
Continuous Current allowable through
isolator
700mA (max)
Isolator Resistance in closed state
0.13Ω (max)
Leakage Current into direct short
circuit with isolator open
13mA (max)
Parallel Fault Resistance to be seen at
the Control Panel for isolators to open
200Ω (typ)
Appendix 4.5
Summary of Contents for MA-1000
Page 2: ...1 ...
Page 3: ...2 ...
Page 15: ...14 MA 1000 ...
Page 17: ...16 Peripheral Devices ...
Page 62: ...61 Appendix 4 9 MA 1000 Site Installer User Manual ...
Page 63: ...62 ...
Page 71: ...70 ...
Page 76: ...75 FIGURE 12 Allocated devices list ...
Page 80: ...79 FIGURE 14 Allocated List ...
Page 84: ...83 6 Select Delete Device button FIGURE 19 Select Device ...
Page 88: ...87 Save as TXT format ...
Page 89: ...88 Panel outputs Save as EXEL format ...
Page 91: ...90 FIGURE 21 View Event 2 History will display automatically in the default browser ...
Page 93: ...92 4 Select Add panel or Delete panel 5 Select Close to apply ...
Page 98: ...97 ...
Page 103: ...102 Fig 1 ...
Page 105: ...104 Appendix 4 12 Detectors UL Certifications ...
Page 106: ...105 ...
Page 107: ...107 ...