Using the drop down box, select the communications port (1-9) that will be used to physically connect to the
panel and then select
Ok
.
6.
Place the panel into
SLC menu setup - CDR
and select the
Learn
or
SCAN Devices
menu options from the
menu choices displayed on the panel.
7.
Select
PC
from the menu choices displayed on the panel and then select
ENTER
.
8.
This must be done
BEFORE
the next step; otherwise communications will not be possible.
9.
Select the Check Connection button on the PC software.
10.
Select the
Read from Panel
button on the PC software (
see FIGURE 2
).
11.
The panel configuration will now be transferred to the PC. If this does not occur, double check the connections
using Check Connection button and repeat these steps again.