Default settings
Default setting will erase all configurations:
CDR (Customer Data Record)
Event history
3.
Loop Loading Rules for MA-1000 1200
Standards Limitation
We therefore allow 200 devices on each loop but limit the maximum number of addressable device on a
panel to 400 totals.
Memory
MA-1000 has extremely powerful output device control capabilities, every output device can be programmed
to provide up to three stages of separate cause and effect programming.
This level of programming requires a large amount of memory to store all the settings and because the
amount of memory is finite, the system has to be restricted to a maximum of 80 outputs made up from
up to 70 sounders per loop (count as 1 output) and 20 output devices of any sort (these all count as 3
outputs)
e.g. 60 sounders and 20 IO’s would be 120 outputs, 70 sounders and 16 IO’s would be 118 outputs.
The rules governing total load still apply
Input devices such as t-Tap do not need to be counted.
Summary of Contents for MA-1000
Page 2: ...1 ...
Page 3: ...2 ...
Page 15: ...14 MA 1000 ...
Page 17: ...16 Peripheral Devices ...
Page 62: ...61 Appendix 4 9 MA 1000 Site Installer User Manual ...
Page 63: ...62 ...
Page 71: ...70 ...
Page 76: ...75 FIGURE 12 Allocated devices list ...
Page 80: ...79 FIGURE 14 Allocated List ...
Page 84: ...83 6 Select Delete Device button FIGURE 19 Select Device ...
Page 88: ...87 Save as TXT format ...
Page 89: ...88 Panel outputs Save as EXEL format ...
Page 91: ...90 FIGURE 21 View Event 2 History will display automatically in the default browser ...
Page 93: ...92 4 Select Add panel or Delete panel 5 Select Close to apply ...
Page 98: ...97 ...
Page 103: ...102 Fig 1 ...
Page 105: ...104 Appendix 4 12 Detectors UL Certifications ...
Page 106: ...105 ...
Page 107: ...107 ...