24
The first row indicates this trouble from a list of all the troubles.
Second - type of trouble.
NO BATTERY
TROUBLE 003/008
System TROUBLE Conditions
The following list contains the system-wide and NAC trouble conditions:
NO BATTERY
Battery removed
LOW BATTERY
Discharged battery less than 22VDC
AC FAULT
AC Voltage not present
CHARGER FAULT
Either a condition stopping the charger to operate or a
failure with the charger has occurred.
GROUND FAULT
Level 9VDC
NAC TROUBLE 1.2.3.4
Open condition, short & ground conditions.
RS485 TROUBLE
Connection to Annunciator or Booster is lost.
This screen is activated when ever one or more of the following condition(s) exist.
NO BATTERY
TROUBLE 003/008
The panel buzzer will activate if a trouble condition exists. In a trouble condition, the
panel displays the zone or devices causing that
condition. The “Trouble” indicator goes
away automatically when the situation causing the trouble condition has been rectified.
To view trouble events by pressing the
keys you are able to manually read the
trouble conditions.
Summary of Contents for MA-1000
Page 2: ...1 ...
Page 3: ...2 ...
Page 15: ...14 MA 1000 ...
Page 17: ...16 Peripheral Devices ...
Page 62: ...61 Appendix 4 9 MA 1000 Site Installer User Manual ...
Page 63: ...62 ...
Page 71: ...70 ...
Page 76: ...75 FIGURE 12 Allocated devices list ...
Page 80: ...79 FIGURE 14 Allocated List ...
Page 84: ...83 6 Select Delete Device button FIGURE 19 Select Device ...
Page 88: ...87 Save as TXT format ...
Page 89: ...88 Panel outputs Save as EXEL format ...
Page 91: ...90 FIGURE 21 View Event 2 History will display automatically in the default browser ...
Page 93: ...92 4 Select Add panel or Delete panel 5 Select Close to apply ...
Page 98: ...97 ...
Page 103: ...102 Fig 1 ...
Page 105: ...104 Appendix 4 12 Detectors UL Certifications ...
Page 106: ...105 ...
Page 107: ...107 ...