76
2.2.8 Configuring MA-1000 Onboard Outputs
To set the operating condition of onboard output circuits, select the
NACs
or
Relays
button, as indicated below in
FIGURE 13
: -
SILENCE
When the Silence key is pressed the NAC turn off.
FIRE
NAC to turn on when a fire alarm condition exists
AUX Continuous
Power supply 24VDC.
AUX Resettable
Power supply 24VDC resettable (lost power for 2 sec after reset).
Door Magnets
A steady 24VDC in an ALARM condition the AUX changes state to OFF until
RESET.
SUPERVISORY
NAC turns on when a supervisory condition exists.
CADENCE
NAC Cadence is where you choose the NAC type ON, March code,
ANSI S-3-41, Single stroke BI, California code, Wheelock.
Delay
Delay time 0-120 sec to trigger Nac On when FIRE NAC is selected.
Each step 10
–sec.
Timer
Timer 0-120 sec to trigger Nac Off when FIRE NAC is selected.
Each step 10
–sec.
Summary of Contents for MA-1000
Page 2: ...1 ...
Page 3: ...2 ...
Page 15: ...14 MA 1000 ...
Page 17: ...16 Peripheral Devices ...
Page 62: ...61 Appendix 4 9 MA 1000 Site Installer User Manual ...
Page 63: ...62 ...
Page 71: ...70 ...
Page 76: ...75 FIGURE 12 Allocated devices list ...
Page 80: ...79 FIGURE 14 Allocated List ...
Page 84: ...83 6 Select Delete Device button FIGURE 19 Select Device ...
Page 88: ...87 Save as TXT format ...
Page 89: ...88 Panel outputs Save as EXEL format ...
Page 91: ...90 FIGURE 21 View Event 2 History will display automatically in the default browser ...
Page 93: ...92 4 Select Add panel or Delete panel 5 Select Close to apply ...
Page 98: ...97 ...
Page 103: ...102 Fig 1 ...
Page 105: ...104 Appendix 4 12 Detectors UL Certifications ...
Page 106: ...105 ...
Page 107: ...107 ...