17
2.4.1 Connecting the AC Power
WARNING!
To reduce the risk of electrical shock, make sure that all power has been turned off or disconnected
prior to attempting to connect power to the Power Supply.
Apply the AC Power BEFORE connecting the batteries to the Panel!
Provide the Fire Alarm Control Panel with a dedicated AC Circuit rated 15 Amps.
Refer to Figure 2.1 for wiring diagram.
1. Enter Power Cable into Cabinet via left side knock out hole.
2. Attach the brown (live) wire from the source to terminal
“Line” (USA use color black wire).
3. Attach the blue (neutral) wire from the source to the “Neutral” terminal (USA use color white wire).
4. Attach the ground wire from the source to the “GD” terminal block (USA use color green wire).
Figure 2.1
P1
Battery
Fault
GND wire
NEUTRAL
LIVE
Normal
+ -
GND
Factory fitted
NO NOT REMOVE
The GND cable must
be connected to this
point
+
-
Summary of Contents for MA-1000
Page 2: ...1 ...
Page 3: ...2 ...
Page 15: ...14 MA 1000 ...
Page 17: ...16 Peripheral Devices ...
Page 62: ...61 Appendix 4 9 MA 1000 Site Installer User Manual ...
Page 63: ...62 ...
Page 71: ...70 ...
Page 76: ...75 FIGURE 12 Allocated devices list ...
Page 80: ...79 FIGURE 14 Allocated List ...
Page 84: ...83 6 Select Delete Device button FIGURE 19 Select Device ...
Page 88: ...87 Save as TXT format ...
Page 89: ...88 Panel outputs Save as EXEL format ...
Page 91: ...90 FIGURE 21 View Event 2 History will display automatically in the default browser ...
Page 93: ...92 4 Select Add panel or Delete panel 5 Select Close to apply ...
Page 98: ...97 ...
Page 103: ...102 Fig 1 ...
Page 105: ...104 Appendix 4 12 Detectors UL Certifications ...
Page 106: ...105 ...
Page 107: ...107 ...